Plan Review Notes For Permit 14081250 |
Permit Number |
14081250 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-09-22 11:30:15 | SITE LIGHTING, BUILDING REVIEW COMMENTS FORE LIGHT | | POLES. | | CODE: 2010 FBC. | | | | 1- A) PROVIDE 2 COPIES OF THE LIGHT POLE MANUFACTURER'S | | SPECIFICATIONS SHOWING THAT THE POLE MEETS THE DESIGN | | CRITERIA SPECIFIED BY IN THE ENGINEER CALCULATIONS | | SUBMITTED. SEC. 107.2.1 CITY AMENDMENTS TO FBC. | | | | B) ENGINEER OF RECORD TO REVIEW AND APPROVE LIGHT POLE | | SPECIFICATIONS PRIOR TO SUBMITTAL. SEC. 107.3.4.1 CITY | | AMENDMENTS. | | | | 2- ENGINEER'S CALCULATIONS SUBMITTED: | | A) NEED ENGINEER'S ORIGINAL SEAL AND SIGNATURE AS | | REQUIRED BY CHAPTER 471 FL. ST. | | | | B) IF ENGINEER IT'S TAKING OVER THE WORK OF ANOTHER | | ENGINEER, THEN HE NEEDS TO REMOVE THE SEAL AND | | SIGNATURE OF THE ORIGINAL ENGINEER AND SEAL AND USE HIS | | OWN TITLE BLOCK, SEAL AND SIGNATURE AS REQUIRED BY SEC. | | 61G15-27.001. FAC. | | | | C) THERE ARE TWO DIFFERENT CALCULATIONS SUBMITTED AND | | THEY THE WERE SIGNED AND SEALED ON DIFFERENT DATES | | ALSO. COORDINATE AS REQUIRED AND RESUBMIT. SEC. 107.2.1 | | CITY AMENDMENTS. | | | | D) THE CALCULATIONS NEED TO MATCH THE HEIGHT AND | | FOOTING INFORMATION SHOWN ON DRAWING PH.01 SUBMITTED. | | REVISE AS REQUIRED TO MATCH. SEC. 107.2.1 CITY | | AMENDMENTS. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICE DEPARTMENT | | (561)805-6712 | | [email protected] |
|