Plan Review Notes For Permit 14081219 |
Permit Number |
14081219 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-09-05 13:49:14 | PERMIT # 14081219 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | PROVISO: ALL TENANT SPACES IN BUILDING 1855 MUST BE | | TIED INTO THE MASTER FIRE ALARM PANEL FOR THE BUILDING. | | EACH TENANT SPACE WILL BE INTERCONNECTED AND UPON | | ACTIVATION OF AN ALARM IN ANY ONE SPACE, ALL SPACES | | WILL HAVE THEIR NOTIFICATION DEVICES ACTIVATE. AN FACP | | IN A TENANT SPACES WILL HAVE THE "RESET" AND "SILENCE" | | FUNCTIONS DEACTIVED. RESET AND SILENCE OF AN ALARM IS | | LIMITED TO THE MASTER PANEL FOR THE BUILDING AND MAY | | ONLY BE DONE BY A LICENSED FIRE ALARM TECHNICIAN. | | SHOULD IT BE FOUND THAT TENANTS ARE ACCESSING THE | | PANELS IN THE TENANT SPACES AND/OR USING THE "RESET" OR | | "SILENCE" FUNCTIONS, THE OFFICE OF THE FIRE MARSHAL MAY | | REQUIRE THAT THE TENANT FACP BE REMOVED. | | | | | | SUE ELLEN CALDERON | | FIRE INSPECTOR & INVESTIGATOR | | OFFICE OF THE FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | (561) 804-4751 | | |
|