Plan Review Notes For Permit 14081208 |
Permit Number |
14081208 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2014-10-10 15:26:19 | 10/10/2014 | | PROJECT: GRAND ILLUSIONS | | PERMIT#: 14081208 | | CODE: 2008 EDITION OF THE NEC | | 2010 EDITION OF THE FBC | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | ELECTRICAL PLAN REVIEW | | ACTION: PROVISO | | | | 1) NEC 430.102 LOCATION. | | AN INDIVIDUAL DISCONNECTING MEANS SHALL BE PROVIDED FOR | | EACH CONTROLLER AND SHALL DISCONNECT THE CONTROLLER. | | THE DISCONNECTING MEANS SHALL BE LOCATED IN SIGHT FROM | | THE CONTROLLER LOCATION | | | | 2) SEPARATE ELECTRICAL PERMIT APPLICATIONS IS REQUIRED | | FOR INSTALLATION OF ELECTRICAL | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. SEE LINK: | | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ | | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO | | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED | | SHEETS FOR COMPARATIVE REVIEW. | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] | | |
|