Plan Review Notes For Permit 14081199 |
Permit Number |
14081199 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-09-02 11:32:24 | FBC 2010, 1ST REVIEW: | | | | THE SUBMITTAL IS INSUFFICIENT IN TERMS OF SETS, FORMS, | | SUBMITTAL DOCUMENTS AND DEFINED SCOPE OF WORK. | | | | FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF | | CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL | | INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL | | BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT | | APPLICATION. | | | | FBC-107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. ALL | | INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING | | DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON | | RESPONSIBLE FOR THE DESIGN. | | | | FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS | | SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON | | SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. | | THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, | | SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO | | RECORDS MANAGEMENT. | | | | FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE | | PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 REVIEWED | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD AS | | MAY BE APPLICABLE. | | | | FBC 107.3.5.1.1(8) - PROVIDE WIND DESIGN LOADS/DESIGN | | PRESSURES PURSUANT TO FBC-CHAPTER 16 OR UTILIZE THE | | SHUTTER INSTALLATION SCHEDULE FORM AVAILABLE AT | | WPB.ORG. | | | | STEVEN KENNEDY, CBO | | CHIEF PLANS EXAMINER | | (561) 805-6710 | | [email protected] | | |
|