Plan Review Notes For Permit 14081171 |
Permit Number |
14081171 |
|
Review Stop |
B |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2015-01-20 08:54:29 | ****PROVISO**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | INSTALLATION SCHEDULE DID NOT INCLUDE THE FOLLOWING | | INFORMATION: | | | | SHUTTER CONNECTION MOUNTING TYPE (SHOULD CORRELATE WITH | | THE ANCHOR CHARTS ON PAGE 4 OF THE NOA; EITHER C1, C2, | | C3, C4, OR C5) | | ANCHOR SPACING | | | | THEREFORE, INSTALLATION SCHEDULE HAS BEEN REDLINED FOR | | WORST CASE (C5, 5" ANCHOR SPACING) | | | | IF THIS IS NOT ACCEPTABLE, SUBMIT A REVISION WHICH | | INCLUDES A REVISED INSTALLATION SCHEDULE WITH SHUTTER | | CONNECTION MOUNTING TYPE AND ANCHOR SPACING PROPOSED; | | OR, DO NOT PICK UP THIS PERMIT AND RESUBMIT WITH A | | REVISED INSTALLATION SCHEDULE. | | | | LOCATION FOR INFILL DETAIL 2-A1 IS NOT SHOWN ON THE | | FLOOR PLAN. IF THIS IS TO BE USED, SUBMIT A REVISED | | PLAN SHOWING PROPOSED LOCATION. | | | | INFILL DETAIL 2-A1 LACKS A BOND BREAK, FBC 2010 | | RESIDENTIAL 703.6.3. IF THIS IS TO BE USED, REVISE | | DETAIL ANS SUBMIT. | | | | | | | | |
|