2015-01-20 09:19:02****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. COMPLETE THE SAMPLE INSTALLATION SCHEDULE OR PROVIDE
 ALL INFORMATION TO SHOW CODE COMPLIANCE IN ANOTHER
 FORMAT, FBC*106, FBC R301, FBC1609. TWO SETS REQUIRED.
 THIS FORM IS AVAILABLE IN THE LOBBY OR ON THE INTERNET
 AT
  
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/SCHEDULE_FOR_INSTALLATION.PDF
  
 2. THE STORM PANEL NOA NUMBER ON THE PLAN IS NOT
 CONSISTENT WITH THE NUMBER OF THE PRODUCT APPROVAL
 SUBMITTED, FBC 107. PLEASE CORRELATE.
  
 3. PLAN DOES NOT INDICATE WHERE THE INFILL DETAIL 2-A1
 WILL BE INSTALLED, FBC 107.
  
 4. BOND BREAK REQUIRED, REVISE INFILL DETAIL 2-A1, FBC
 2010 RESIDENTIAL 703.6.3.
  
  
  