Plan Review Notes For Permit 14081169 |
Permit Number |
14081169 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2015-01-20 09:08:28 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2010 | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | 1. COMPLETE THE SAMPLE INSTALLATION SCHEDULE OR PROVIDE | | ALL INFORMATION TO SHOW CODE COMPLIANCE IN ANOTHER | | FORMAT, FBC*106, FBC R301, FBC1609. TWO SETS REQUIRED. | | THIS FORM IS AVAILABLE IN THE LOBBY OR ON THE INTERNET | | AT | | | | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ | | 2013/09/SCHEDULE_FOR_INSTALLATION.PDF | | | | 2. THE STORM PANEL NOA NUMBER ON THE PLAN IS NOT | | CONSISTENT WITH THE NUMBER OF THE PRODUCT APPROVAL | | SUBMITTED, FBC 107. PLEASE CORRELATE. | | | | 3. PLAN DOES NOT INDICATE WHERE THE INFILL DETAIL 2-A1 | | WILL BE INSTALLED, FBC 107. | | | | 4. BOND BREAK REQUIRED, REVISE INFILL DETAIL 2-A1, FBC | | 2010 RESIDENTIAL 703.6.3. | | | | | | |
|