2014-08-29 14:53:28 | 2010 FGC & 2010 WPB ADMIN. AMEND. TO 2010 FBC |
| SEC.107.2.1. |
| 1) INDICATE ON BOTH PLANS THE TYPE OF PIPE MATERIAL TO |
| BE INSTALLED. |
| 2) SHOW THE LOCATION OF THE METER ON BOTH SETS OF |
| PLANS. |
| 3) SHOW THE TOTAL LENGTH OF PIPING FROM THE POINT OF |
| DELIVERY TO THE MOST REMOTE OUTLET OF THE SYSTEM ON |
| BOTH PLANS. 2010 FGC 402.4.1. |
| 4) SUBMIT TWO COPIES OF THE APPLICABLE PIPE SIZING |
| TABLE FROM THE FUEL GAS CODE FOR THIS SYSTEM. |
| 5) THE TOTAL BTU LOAD ON THIS SYSTEM IS 319,500 NOT |
| 319,000. REVISE THE BTU LOAD ON BOTH PLANS. |
| 6) SHOW THE LOCATION OF THE GAS METER, THE 2 PSI |
| REGULATOR AND SECOND STAGE REGULATOR. |
| 7) EXPLAIN THE STATEMENT "TANKLESS GO BOTH SIDE AT |
| MASTER BATH." I DO NOT UNDERSTAND THIS STATEMENT. |
| 8) THE PAGES FROM THE KB SERIES MANUAL HAS SOME OF THE |
| THE INFORMATION CUT OFF OF THE SHEETS. SUBMIT FULL |
| PAGES. SEE SHEETS 7-9. |
| 9) YOU HAVE CIRCLED MODEL # RU80E FOR THE TANKLESS |
| WATER HEATER BUT THE ADDITIONAL PAGES ARE FOR MODEL # |
| RU 98E. SUBMIT THE CORRECT PAGES FOR THE UNIT BEING |
| INSTALLED. |
| 10) THE SUBMITTED DOCUMENTS FOR THE VIKING RANGETOP, |
| THE SIDE BURNER AND THE GRILL DO NOT SHOW THAT THE |
| UNITS ARE LABELED AND LISTED PER THE 2010 FGC |
| SEC.301.3. SUBMIT SPECIFICATION SHEETS FROM THE |
| MANUFACTURER, NOT FROM A WEBSITE SHOPPING ADDRESS. |
| 11) YOUR PERMIT IS FOR NATURAL GAS YET THE PAPERWORK |
| FOR THE GRILL SHOWS THE GRILL AS PROPANE. CLARIFY. |
| |
| ** IN THE FUTURE, DO NOT SUBMIT PLANS DRAWN IN PENCIL. |
| |