Plan Review Notes
Plan Review Notes For Permit 14081157
Permit Number 14081157
Review Stop G
Sequence Number 1
Notes
Date Text
2014-08-29 14:53:282010 FGC & 2010 WPB ADMIN. AMEND. TO 2010 FBC
 SEC.107.2.1.
 1) INDICATE ON BOTH PLANS THE TYPE OF PIPE MATERIAL TO
 BE INSTALLED.
 2) SHOW THE LOCATION OF THE METER ON BOTH SETS OF
 PLANS.
 3) SHOW THE TOTAL LENGTH OF PIPING FROM THE POINT OF
 DELIVERY TO THE MOST REMOTE OUTLET OF THE SYSTEM ON
 BOTH PLANS. 2010 FGC 402.4.1.
 4) SUBMIT TWO COPIES OF THE APPLICABLE PIPE SIZING
 TABLE FROM THE FUEL GAS CODE FOR THIS SYSTEM.
 5) THE TOTAL BTU LOAD ON THIS SYSTEM IS 319,500 NOT
 319,000. REVISE THE BTU LOAD ON BOTH PLANS.
 6) SHOW THE LOCATION OF THE GAS METER, THE 2 PSI
 REGULATOR AND SECOND STAGE REGULATOR.
 7) EXPLAIN THE STATEMENT "TANKLESS GO BOTH SIDE AT
 MASTER BATH." I DO NOT UNDERSTAND THIS STATEMENT.
 8) THE PAGES FROM THE KB SERIES MANUAL HAS SOME OF THE
 THE INFORMATION CUT OFF OF THE SHEETS. SUBMIT FULL
 PAGES. SEE SHEETS 7-9.
 9) YOU HAVE CIRCLED MODEL # RU80E FOR THE TANKLESS
 WATER HEATER BUT THE ADDITIONAL PAGES ARE FOR MODEL #
 RU 98E. SUBMIT THE CORRECT PAGES FOR THE UNIT BEING
 INSTALLED.
 10) THE SUBMITTED DOCUMENTS FOR THE VIKING RANGETOP,
 THE SIDE BURNER AND THE GRILL DO NOT SHOW THAT THE
 UNITS ARE LABELED AND LISTED PER THE 2010 FGC
 SEC.301.3. SUBMIT SPECIFICATION SHEETS FROM THE
 MANUFACTURER, NOT FROM A WEBSITE SHOPPING ADDRESS.
 11) YOUR PERMIT IS FOR NATURAL GAS YET THE PAPERWORK
 FOR THE GRILL SHOWS THE GRILL AS PROPANE. CLARIFY.
  
 ** IN THE FUTURE, DO NOT SUBMIT PLANS DRAWN IN PENCIL.
  