Plan Review Notes
Plan Review Notes For Permit 14081143
Permit Number 14081143
Review Stop M
Sequence Number 1
Notes
Date Text
2014-09-22 11:16:47PLEASE CLARIFY M4.1
 THE AIR BALANCE / VENTILATION CALCS / FANN SCHEDULE
 SHOW THE TOILET ROOMS AS BEING PUBLIC WITH NO CFM'S
 BEING CALCULATED ON THE VENTILATION SCHEDULE BUT THE
 FAN SCHEDULE
 INDICATES 50 CFM EACH (100 CFM) AS PER THE AIR BALANCE,
 YET THE AIR BALANCE SUBTRACTS THIS FROM THE TOTAL CFM
 REQUIRED