2014-08-28 11:55:58BUILDING PLAN REVIEW
 PERMIT: 14081143
 ADD: 303 BANYAN BLVD
 CONT: IBIS BUILDING
 TEL: (561)318-3408
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. AUG. 28/2014
 ACTION: DENIED
  
 1) SHEET A1.1 VERSES THE STRUCTURAL SHEETS. THE PLANS
 ARE NOT CLEAR TO THE BACK 1/3RD OF THE TENANT SUITE IF
 THE CONCRETE FLOOR IS BEING REMOVED OR IS THE STEEL
 FRAMING BELOW BEING REPLACED? THERE IS NO NOTE ON THE
 A1.1 UNDER THE DEMO NOTES THIS FLOOR IS BEING REMOVED.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1.3. ADDITIONAL
 INFORMATION IS REQUIRED.
  
 2) SHEET A1.1 LIST THE COMMON PATH OF TRAVEL FROM THE
 BACK CORNER OF THE RESTROOM TO THE FRONT ENTRY 107 FT.
 THAT EXCEEDS THE COMMON PATH OF TRAVEL EXCEPTION # 1 OF
 1014.3 OF 100 FT. WOULDN'T THE COMMON PATH OF TRAVEL
 STOP AT THE REAR EXIT.
  
 3) OFFICE # 104 THE INSWING DOOR DOES NOT HAVE THE
 REQUIRED 18 INCHES LATCH SIDE OF DOOR. 2010
 FBC-ACCESSIBILITY CODE 404.2.4.1 AND TABLE 404.2.4.1.
  
 4A) A1.1 SHOWS A 2HR RATED STAIR ENCLOSURE, SHEET A.2.1
 SHOWS A WALL INFILL, WALL IDENTIFICATION TAG W3. PLEASE
 REVIEW SHEET A3.1 WALL TYPES. THE WRITTEN WORD DOES NOT
 LINE UP WITH THE DETAILS, NOT SURE WHICH DETAIL TIES TO
 WHICH WALL TYPE. DISCREPANCY IN PLANS. 107.2.1.3.
  
 4B) SHEET A3.1 WALL IDENTIFICATION TAGS, 2 WALL TYPES
 INDICATE A UL DESIN NUMBER, U419 & U465. NEITHER
 PROVIDE A DETAIL OF THESE ASSEMBLIES. NOTE U-419 CAN BE
 1-4 HOUR RATING, WHICH ARE YOU DESIGNING TOO?
  
 4C) SHEET A2.1, A3.1 AND S-1 DISCREPANCY IN PLANS. THE
 INFILL WALL OF THE 2 HR RATED EXIT ENCLOSRE ON THE
 SHEET S-1 INDICATES THE USE OF 8 INCH CMU. 107.2.1.3
 DISCREPANCY IN PLANS, ADDITIONAL INFORMATION IS
 REQUIRED.
  
 5) SHEET S-2 INDICATES TH USE OF 20 GAUGE STUDS, IN 20
 GAUGE STUDS THERE ARE (2) THICKNESSES, PLEASE SPECIFY,
 DRYWALL 30(MILS) AND STRUCTURAL 33(MILS)?
  
 6) SHEET A 2.1 & A4.1 BOTH INDICATE A NEW EXTERIOR
 DOOR, PLEASE PROVIDE COMPLIANCE WITH: 2010 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41 COMPONENTS
 & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
  
  
 7) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]