Plan Review Notes For Permit 14081140 |
Permit Number |
14081140 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-09-08 13:15:14 | DATE: 9/8/2014 | | PROJECT: SUITE 302 BANYAN BUILDING | | PERMIT#: 14081140 | | CODE: 2008 EDITION OF THE NEC | | 2010 EDITION OF THE FBC | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | 1ST ELECTRICAL PLAN REVIEW | | ACTION: DENIED | | | | 1) THE WIRE INDICATED AS FEEDING PANEL MDP3 IS NOT | | APPROVED FOR 1200AMPS. PROVIDE A PANEL SCHEDULE AND A | | LOAD CALCULATION FOR PANEL MDP3. WPB AMENDMENTS TO THE | | FBC SECTION 107.3.5 | | | | 2) PROVIDE MANUFACTURER SPECIFICATIONS ON THE FLOOR BOX | | SPECIFIED FOR THE CONFERANCE ROON AND EXECUTIVE OFFICE. | | BOXES LISTED SPECIFICALLY FOR THIS APPLICATION SHALL BE | | USED FOR RECEPTACLES LOCATED IN THE FLOOR. NEC | | 314.27(C). | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. SEE LINK: | | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ | | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO | | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED | | SHEETS FOR COMPARATIVE REVIEW. | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] | | |
|