2014-09-08 13:15:14DATE: 9/8/2014
 PROJECT: SUITE 302 BANYAN BUILDING
 PERMIT#: 14081140
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) THE WIRE INDICATED AS FEEDING PANEL MDP3 IS NOT
 APPROVED FOR 1200AMPS. PROVIDE A PANEL SCHEDULE AND A
 LOAD CALCULATION FOR PANEL MDP3. WPB AMENDMENTS TO THE
 FBC SECTION 107.3.5
  
 2) PROVIDE MANUFACTURER SPECIFICATIONS ON THE FLOOR BOX
 SPECIFIED FOR THE CONFERANCE ROON AND EXECUTIVE OFFICE.
 BOXES LISTED SPECIFICALLY FOR THIS APPLICATION SHALL BE
 USED FOR RECEPTACLES LOCATED IN THE FLOOR. NEC
 314.27(C).
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  