Plan Review Notes For Permit 14081129 |
Permit Number |
14081129 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-08-28 14:43:03 | DATE: 8/28/2014 | | PROJECT: ASV LLC | | PERMIT#: 14081129 | | CODE: 2008 EDITION OF THE NEC | | 2010 EDITION OF THE FBC | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | 1ST ELECTRICAL PLAN REVIEW | | ACTION: DENIED | | | | 1) THE WIRE IN THE RISER IS NOT ADAQUATE SIZE FOR A | | SERVICE ENTRRANCE CONDUCTOR ON A 150AMP MAIN BREAKER | | SERVICE. PLEASE ADJUST THE RISER DIAGRAM TO REFLECT THE | | CORRECT WIRE SIZES. NEC 310.16 | | | | 2) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF | | THE PERSON RESPONSIBLE FOR THE DESIGN. WPB AMENDMENTS | | TO FBC 107.2.1 | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. SEE LINK: | | HTTP://WPB.ORG/DEVELOPMENT | | /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM | | ITTAL_FORM_04132010.PDF | | | | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO | | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED | | SHEETS FOR COMPARATIVE REVIEW. | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] | | |
|