Plan Review Notes For Permit 14081093 |
Permit Number |
14081093 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-09-18 13:42:10 | 14081093 | | 4847 FRED GLADSTONE DRIVE | | GENERATOR PROJECT. ATS BUILDING | | | | REVIEWED WITH THE FOLLOWING COMMENTS NOTED ON THE PLAN. | | | | VERIFY A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION | | FOR THE ELECTRIC SERVICE, PANEL BOARDS, TRANSFER | | SWITCHES AND MAIN DISCONNECTING MEANS HAS BEEN | | PROVIDED. NEC 110.16, 110.22 | | | | VERIFY THAT THE REQUIRED DEDICATED EQUIPMENT SPACES | | WITH SAFE WORKING CLEARANCE FOR THE ELECTRICAL | | EQUIPMENT, DISCONNECTS AND TRANSFER SWITCHES HAVE BEEN | | PROVIDED. NEC 110.26 | | | | | | ROBERT LECKY, CBO | | ELECTRICAL PLANS REVIEW | | 561-373-3701 | | [email protected] | | | | |
|