2015-01-08 09:23:16!) THE STANCOR DUPLEX OIL-MINDER SPECIFICATION SHEETS
 CALL OUT DUPLEX PUMPS AND A 55 GAL OIL STORAGE
 CONTAINER BUT THE PLANS ONLY SHOW THE DISCHARGE OF ONE
 PUMP. CLARIFY.
 2) SHOW THE LOCATION OF THE OIL STORAGE CONTAINER AND
 THE CONTROL PANEL ON THE PLANS. WPB AMEND. TO 2010 FBC
 SEC.107.2.1. 2ND REQUEST. THE SHOP DRAWING MENTIONED
 AND SUBMITTED DOES NOT IDENTIFY THE TANKS,
 LOCATION,ETC.
 3) IF THIS IS A TWO PUMP SYSTEM, SUBMIT A PIPING
 DIAGRAM SHOWING THE PIPING, OIL CONTAINER,& DISCHARGE
 POINT.
 WPB AMEND. TO 2010 FBC SEC.107.2.1.
 4) SUBMIT DOCUMENTATION THAT SHOWS THAT THESE
 COMPONENTS ARE CERTIFIED BY A NATIONALLY RECOGNIZED
 INDEPENDENT TESTING LABORATORY AS STATED IN THE STANCOR
 SPECIFICATIONS. WPB AMEND. TO 2010 FBC SEC.107.2.1.
 5) A CHECK VALVE SHALL BE INSTALLED ON THE PUMP SIDE OF
 THE SHUTOFF VALVE PER THE 2010 FPC SEC.712.2.
  