Plan Review Notes For Permit 14081026 |
Permit Number |
14081026 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2014-11-03 12:17:21 | 1) SHOW THE LOCATION OF THE HOLDING TANK AND CONTROL | | PANEL FOR THIS SYSTEM. WPB AMEND. TO FBC SEC. 107.2.1. | | 2) SUBMIT DOCUMENTATION THAT SHOWS THAT THIS UNIT IS | | CERTIFIED BY A NATIONALLY RECOGNIZED INDEPENDENT | | TESTING LABORATORY AS STATED IN THE LITERATURE THAT WAS | | SUBMITTED. WPB AMEND. TO FBC SEC. 107.2.1. | | 3) SHT. P-2 - THE PARTIAL PLUMBING RISER READS " SUMP | | PUMP - SEE DETAIL SHT. P-2 - THERE IS NO SUCH DETAIL ON | | SHT. P-2. CLARIFY. | | 4) 712.2 VALVES REQUIRED. | | A CHECK VALVE AND A FULL OPEN VALVE LOCATED ON THE | | DISCHARGE SIDE OF THE CHECK VALVE SHALL BE INSTALLED IN | | THE PUMP OR EJECTOR DISCHARGE PIPING BETWEEN THE PUMP | | OR EJECTOR AND THE GRAVITY DRAINAGE SYSTEM. ACCESS | | SHALL BE PROVIDED TO SUCH VALVES. SUCH VALVES SHALL BE | | LOCATED ABOVE THE SUMP COVER REQUIRED BY SECTION 712.1 | | OR, WHERE THE DISCHARGE PIPE FROM THE EJECTOR IS BELOW | | GRADE, THE VALVES SHALL BE ACCESSIBLY LOCATED OUTSIDE | | THE SUMP BELOW GRADE IN AN ACCESS PIT WITH A REMOVABLE | | ACCESS COVER. | | THE SUMP PIT SHALL BE FITTED WITH A GAS-TIGHT REMOVABLE | | COVER ADEQUATE TO SUPPORT ANTICIPATED LOADS IN THE AREA | | OF USE. THE SUMP PIT SHALL BE VENTED IN ACCORDANCE WITH | | CHAPTER 9. | | 5) SUBMIT MANUF. SPECS FOR THE PUMPS. PUMPS SHALL MEET | | THE CRITERIA OF 2010 FPC TABLE 712.4.2. | | | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | | | | | | | | | | | |
|