2014-08-27 12:16:50PLUMBING PLAN REVIEW
 PERMIT: 14081026
 ADD: 222 LAKEVIEW AVE.
 CONT: FASTRACK
 TEL: (561)304-7881
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: WED. AUG. 27/2014
 ACTION: DENIED
  
 1) SHEET P2 NOTE NOTE # 3 INDICATES THE INSTALATION OF
 A STANCOR OIL MINDER. PLEASE PROVIDE THE MANUFACTURER
 SPECIFICATIONS FOR CODE COMPLIANCE WITH 2010 FBC-P
 1003.4 OIL SEPARATORS REQUIRED.
 AT REPAIR GARAGES, CAR-WASHING FACILITIES, AT FACTORIES
 WHERE OILY AND FLAMMABLE LIQUID WASTES ARE PRODUCED AND
 IN HYDRAULIC ELEVATOR PITS, SEPARATORS SHALL BE
 INSTALLED INTO WHICH ALL OIL-BEARING, GREASE-BEARING OR
 FLAMMABLE WASTES SHALL BE DISCHARGED BEFORE EMPTYING
 INTO THE BUILDING DRAINAGE SYSTEM OR OTHER POINT OF
 DISPOSAL.
 EXCEPTION: AN OIL SEPARATOR IS NOT REQUIRED IN
 HYDRAULIC ELEVATOR PITS WHERE AN APPROVED ALARM SYSTEM
 IS INSTALLED.
  
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  