2014-08-27 15:25:15 | BUILDING PLAN REVIEW |
| PERMIT: 14081026 |
| ADD: 222 LAKEVIEW AVE. |
| CONT: FASTRACK |
| TEL: (561)304-7881 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 1ST REVIEW |
| DATE: WED. AUG. 27/2014 |
| ACTION: PASSED. |
| |
| 1) THIS IS A HIGHRISE BUILDING, THE 2010 FBC-B 708.14.1 |
| REQUIRES ELEVATOR LOBBIES EVEN IF THIS PORTION OF THE |
| BUILDING IS ONLY 5 STORIES TALL OR MEET ONE OF THE |
| SEVEN EXCEPTIONS, THIS IS CONSIDERED NEW WORK. 2010 |
| EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. THE M3 SHEET |
| DOES SHOW SF-1 FAN PRESSURIZING THE ELEVATOR SHAFTWAY. |
| THE SHEET M2 NOTE2 ONCE THE SMOKE ALARM CLOSES VANT # |
| 1, THE VENTS LABELED # 2 WILL OPEN ON ACTUATION OF |
| SMOKE ALARM OTHERWISE THEY ARE SET AND OPERATE AS A |
| BAROMETER PRESSURE SENSOR. |
| |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| DEVELOPMENT SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |
| MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| |