Plan Review Notes
Plan Review Notes For Permit 14081026
Permit Number 14081026
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2014-08-25 14:48:27THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE PROPOSED PLAN DOES NOT INDICATE THE DESIGNATION OF
 AN ELEVATOR LOBBY AND SMOKE PROTECTION ON ANY FLOOR
 LEVEL.
  
 NFPA 101 FLORIDA, 2010 EDITION
  
 7.2.13 ELEVATORS
 7.2.13.3 ELEVATOR LOBBY EVERY FLOOR SERVED BY THE
 ELEVATOR SHALL HAVE AN ELEVATOR LOBBY. BARRIERS FORMING
 THE ELEVATOR LOBBY SHALL HAVE A MINIMUM 1-HOUR FIRE
 RESISTIVE RATING AND SHALL BE ARRANGED AS A SMOKE
 BARRIER IN ACCORDANCE WITH SECTION 8.5.
  
 7.2.13.9 ELEVATOR OPERATIONS. ELEVATORS SHALL BE
 PROVIDED WITH FIRE FIGHTERS EMERGENCY OPERATIONS IN
 ACCORDANCE WITH ASME A 17.A/CSA B44, SAFET CODE FOR
 ELEVATORS AND ESCALATORS.
  
 PLEASE RESUBMIT A PLAN THAT INDICATES THE ELEVATOR
 LOBBY, FIRE FIGHTER EMERGENCY OPERATIONS AND THE MEANS
 TO PROVIDE SMOKE PROTECTION.