Plan Review Notes For Permit 14080967 |
Permit Number |
14080967 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-09-09 16:20:12 | 1ST REVIEW: FBC 2010 | | | | FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE | | PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 REVIEWED | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | SPECIFICALLY, WINDOW, AND DOOR SUBMITTALS. THE | | ARCHITECT, MICHAEL E. SIPULA, INDICATES THE WINDOWS AND | | DOORS WILL BE BY SEPARATE PERMIT YET THEY ARE INCLUDED | | HERE. ALTHOUGH THERE IS A GENERIC WIND CHART, NOT SITE | | SPECIFIC, FROM FRANK BERNARDO, THERE IS NO EVEDENCE | | UPON THE PRODUCT APPROVALS BY A DESIGN PROFESSIONAL FOR | | USE WITH THIS PLAN. | | | | PROVIDE SPECIFICATIONS ON ANY PROPOSED FLOORING | | UNDERLAYMENT DEMONSTRATING COMPLIANCE WITH THE | | FOLLOWING SECTIONS: | | | | FBC 1207.2 AIR-BORNE SOUND. | | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES | | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM | | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION | | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) | | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM | | E 90. | | AND FBC 603.1 FLAME SPREAD . | | | | STEVEN KENNEDY, CBO | | CHIEF PLANS EXAMINER | | (561) 805-6710 | | [email protected] | | |
|