Plan Review Notes
Plan Review Notes For Permit 14080956
Permit Number 14080956
Review Stop P
Sequence Number 1
Notes
Date Text
2014-09-17 12:17:58PHARMACY-
 1) SUBMIT THE CORRECT OCCUPANT LOAD FOR THE PHARMACY.
 THE OCCUPANT LOAD SHALL BE CALCULATED PER TABLE
 1004.1.1 OF THE 2010 FBC WHICH IS 30 SQ. FT. PER PERSON
 GROSS FOR MERCANTILE.
 2) SEPARATE SANITARY FACILITIES ARE REQUIRED FOR MALES
 AND FEMALES IN ACCORDANCE WITH TABLE 403.1 OF THE 2010
 FLORIDA PLUMBING CODE AND SEC.403.2.
 3) THE DRINKING FOUNTAINS APPEAR TO IMPEDE THE MEANS OF
 EGRESS BY PROJECTING INTO THE REQUIRED WIDTH OF THE
 COMMON PATH OF EGRESS TRAVEL PER THE 2010 FBC
 SEC.1003.3.3.
 4) PROVIDE DETAILS AS TO THE TYPE OF WORK WHICH WILL BE
 DONE IN THE "STERILIZATION" AREA.
 5) SIZE ALL SECTIONS OF THE SANITARY RISER.WPB ADMIN.
 AMEND. TO 2010 FBC SEC.107.2.1.
 6) SUBMIT A WATER RISER FOR REVIEW.WPB AMEND. TO 2010
 FBC SEC. 107.3.5.1.3.
 7) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 AUTOCLAVE AND THE TANKLESS WATER HEATER.
 8) SHOW THE MOUNTING HEIGHTS OF THE TOILET PAPER
 DISPENSER, SANITARY NAPKIN RECEPTACLE AND THE PAPER
 TOWEL DISPENSER/RECEPTACLE. COMPLY W/ 2010 FL.
 ACCESSIBILITY CODE SEC. 308.
 9) CLEANOUTS ARE REQUIRED IN THE BASE OF ALL STACKS ON
 THE SANITARY RISER. 2010 FPC SEC. 708.3.4.
 10) SHT. C-1 SHOWS AN 1 1/4" WATER SERVICE TO THE
 BUILDING AND SHT. P-1 SHOWS 1 ". CLARIFY.
 11) SUBMIT STORM DRAINAGE CALCULATIONS FOR THE PHARMACY
 ROOF. ONE-HALF OF THE AREA OF THE PARAPET WALL SHALL
 ALSO BE INCLUDED IN THE CALCULATIONS PER THE 2010 FPC
 SEC. 1106.4.
 12) THE DRINKING FOUNTAINS ARE NOT SHOWN ON THE
 SANITARY RISER. WPB ADMIN. AMEND. TO 2010 FBC
 SEC.107.2.1.
 13) THE SIZING OF THE SCUPPERS SHALL COMPLY WITH TABLE
 1106.7 OF THE 2010 FPC.
  
 WAREHOUSE-
 1) SHOW THE DIMENSION OF THE SHOWER (LXW) ON THE FLOOR
 PLAN. THE SHOWER SHALL BE A MIN. OF 30 INCHES IN WIDTH
 AND A MIN. OF 900 SQ. INCHES PER SEC.417.4.
 2) SHOW THE CORRECT OCCUPANT LOAD FOR THE WAREHOUSE.
 THE OCCUPANT LOAD SHALL BE CALCULATED PER TABLE
 1004.1.1 OF THE 2010 FBC WHICH IS 300 SQ. FT.PER PERSON
 GROSS FOR STORAGE.
 3) THE DOOR ON BATHROOM #107 CANNOT SWING INTO THE
 CLEAR FLOOR SPACE FOR ANY FIXTURE PER THE 2010 FL.
 ACCESS. CODE SEC. 603.2.3.
 4) SUBMIT A WATER RISER FOR REVIEW.WPB AMEND. TO 2010
 FBC SEC. 107.3.5.1.3.
 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 TANKLESS WATER HEATER.
 6) SHOW THE MOUNTING HEIGHTS OF THE TOILET PAPER
 DISPENSER, SANITARY NAPKIN RECEPTACLE AND THE PAPER
 TOWEL DISPENSER/RECEPTACLE. COMPLY W/ 2010 FL.
 ACCESSIBILITY CODE SEC. 308.
 7) SHT. C-1 SHOWS AN 1 1/4" WATER SERVICE TO THE
 BUILDING AND SHT. P-1 SHOWS 1 ". CLARIFY.
 8) CLEANOUTS ARE REQUIRED IN THE BASE OF ALL STACKS ON
 THE SANITARY RISER. 2010 FPC SEC. 708.3.4.
 9) SUBMIT STORM DRAINAGE CALCULATIONS FOR THE WAREHOUSE
 ROOF. ONE-HALF OF THE AREA OF THE PARAPET WALL SHALL
 ALSO BE INCLUDED IN THE CALCULATIONS PER THE 2010 FPC
 SEC. 1106.4.
 10)THE SIZING OF THE SCUPPERS SHALL COMPLY WITH TABLE
 1106.7 OF THE 2010 FPC.
 11) SHT. P-1 REFERS TO GAS PIPING. SUBMIT A GAS RISER
 FOR REVIEW OR DELETE THE NOT IF IT IS NOT APPLICABLE.
 12) SHOW THE LOCATION OF THE TANKLESS WATER HEATER ON
 THE PLAN.
 13) SHOW THE LOCATION AND SUBMIT SPECS ON THE WATER
 FILTRATION SYSTEM. WHAT TYPE OF SYSTEM IS IT, UNDER THE
 SINK? CLARIFY.
 14) SHT. P-1 SHOWS THE CONDENSATE LINE MARKED AS 1/2"
 H. CLARIFY.
 15) SUBMIT DETAIL ON DRYWELL.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  