2014-09-17 12:17:58 | PHARMACY- |
| 1) SUBMIT THE CORRECT OCCUPANT LOAD FOR THE PHARMACY. |
| THE OCCUPANT LOAD SHALL BE CALCULATED PER TABLE |
| 1004.1.1 OF THE 2010 FBC WHICH IS 30 SQ. FT. PER PERSON |
| GROSS FOR MERCANTILE. |
| 2) SEPARATE SANITARY FACILITIES ARE REQUIRED FOR MALES |
| AND FEMALES IN ACCORDANCE WITH TABLE 403.1 OF THE 2010 |
| FLORIDA PLUMBING CODE AND SEC.403.2. |
| 3) THE DRINKING FOUNTAINS APPEAR TO IMPEDE THE MEANS OF |
| EGRESS BY PROJECTING INTO THE REQUIRED WIDTH OF THE |
| COMMON PATH OF EGRESS TRAVEL PER THE 2010 FBC |
| SEC.1003.3.3. |
| 4) PROVIDE DETAILS AS TO THE TYPE OF WORK WHICH WILL BE |
| DONE IN THE "STERILIZATION" AREA. |
| 5) SIZE ALL SECTIONS OF THE SANITARY RISER.WPB ADMIN. |
| AMEND. TO 2010 FBC SEC.107.2.1. |
| 6) SUBMIT A WATER RISER FOR REVIEW.WPB AMEND. TO 2010 |
| FBC SEC. 107.3.5.1.3. |
| 7) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| AUTOCLAVE AND THE TANKLESS WATER HEATER. |
| 8) SHOW THE MOUNTING HEIGHTS OF THE TOILET PAPER |
| DISPENSER, SANITARY NAPKIN RECEPTACLE AND THE PAPER |
| TOWEL DISPENSER/RECEPTACLE. COMPLY W/ 2010 FL. |
| ACCESSIBILITY CODE SEC. 308. |
| 9) CLEANOUTS ARE REQUIRED IN THE BASE OF ALL STACKS ON |
| THE SANITARY RISER. 2010 FPC SEC. 708.3.4. |
| 10) SHT. C-1 SHOWS AN 1 1/4" WATER SERVICE TO THE |
| BUILDING AND SHT. P-1 SHOWS 1 ". CLARIFY. |
| 11) SUBMIT STORM DRAINAGE CALCULATIONS FOR THE PHARMACY |
| ROOF. ONE-HALF OF THE AREA OF THE PARAPET WALL SHALL |
| ALSO BE INCLUDED IN THE CALCULATIONS PER THE 2010 FPC |
| SEC. 1106.4. |
| 12) THE DRINKING FOUNTAINS ARE NOT SHOWN ON THE |
| SANITARY RISER. WPB ADMIN. AMEND. TO 2010 FBC |
| SEC.107.2.1. |
| 13) THE SIZING OF THE SCUPPERS SHALL COMPLY WITH TABLE |
| 1106.7 OF THE 2010 FPC. |
| |
| WAREHOUSE- |
| 1) SHOW THE DIMENSION OF THE SHOWER (LXW) ON THE FLOOR |
| PLAN. THE SHOWER SHALL BE A MIN. OF 30 INCHES IN WIDTH |
| AND A MIN. OF 900 SQ. INCHES PER SEC.417.4. |
| 2) SHOW THE CORRECT OCCUPANT LOAD FOR THE WAREHOUSE. |
| THE OCCUPANT LOAD SHALL BE CALCULATED PER TABLE |
| 1004.1.1 OF THE 2010 FBC WHICH IS 300 SQ. FT.PER PERSON |
| GROSS FOR STORAGE. |
| 3) THE DOOR ON BATHROOM #107 CANNOT SWING INTO THE |
| CLEAR FLOOR SPACE FOR ANY FIXTURE PER THE 2010 FL. |
| ACCESS. CODE SEC. 603.2.3. |
| 4) SUBMIT A WATER RISER FOR REVIEW.WPB AMEND. TO 2010 |
| FBC SEC. 107.3.5.1.3. |
| 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| TANKLESS WATER HEATER. |
| 6) SHOW THE MOUNTING HEIGHTS OF THE TOILET PAPER |
| DISPENSER, SANITARY NAPKIN RECEPTACLE AND THE PAPER |
| TOWEL DISPENSER/RECEPTACLE. COMPLY W/ 2010 FL. |
| ACCESSIBILITY CODE SEC. 308. |
| 7) SHT. C-1 SHOWS AN 1 1/4" WATER SERVICE TO THE |
| BUILDING AND SHT. P-1 SHOWS 1 ". CLARIFY. |
| 8) CLEANOUTS ARE REQUIRED IN THE BASE OF ALL STACKS ON |
| THE SANITARY RISER. 2010 FPC SEC. 708.3.4. |
| 9) SUBMIT STORM DRAINAGE CALCULATIONS FOR THE WAREHOUSE |
| ROOF. ONE-HALF OF THE AREA OF THE PARAPET WALL SHALL |
| ALSO BE INCLUDED IN THE CALCULATIONS PER THE 2010 FPC |
| SEC. 1106.4. |
| 10)THE SIZING OF THE SCUPPERS SHALL COMPLY WITH TABLE |
| 1106.7 OF THE 2010 FPC. |
| 11) SHT. P-1 REFERS TO GAS PIPING. SUBMIT A GAS RISER |
| FOR REVIEW OR DELETE THE NOT IF IT IS NOT APPLICABLE. |
| 12) SHOW THE LOCATION OF THE TANKLESS WATER HEATER ON |
| THE PLAN. |
| 13) SHOW THE LOCATION AND SUBMIT SPECS ON THE WATER |
| FILTRATION SYSTEM. WHAT TYPE OF SYSTEM IS IT, UNDER THE |
| SINK? CLARIFY. |
| 14) SHT. P-1 SHOWS THE CONDENSATE LINE MARKED AS 1/2" |
| H. CLARIFY. |
| 15) SUBMIT DETAIL ON DRYWELL. |
| |