2014-09-25 09:05:38 | | | AREAS NOT ADDRESSED IN THESE PLANS ARE ENERGY, MAKE UP | | AIR (PHARMACY). | | INDICATED ON THE SCHEDULES IS 1 EF, M-1 SHOWS 3. | | SEPERATE THE EQUIPTMENT SCHEDULES, OCCUPANCY LOADS AND | | ENERGY CALCS FOR THE 2 BUILDINGS | | S-4 INDICATES 3 CONDENSERS ON THE PHARMACY AND 2 | | AIRHANDLERS INSIDE. | | THIS MAY NOT BE A COMPLETE LIST OF ITEMS MISSING OR | | INCORRECT. | | CORRECT AND RESUBMIT |
|