2014-09-05 14:30:54 | PLEASE DEMONSTRATE THAT THE FOLLOWING CONDITIONS OF |
| INFORMAL SITE PLAN APPROVAL HAVE BEEN MET: |
| 1.C. APPLY FOR AND RECORD THE UNITY OF TITLE |
| 1.D. DEMONSTRATE THE WORK PROPOSED WITHIN THE EXISTING |
| EASEMENTS IS ACCEPTABLE TO THE EASEMENT HOLDER(S) |
| |
| ALTHOUGH THE CITY'S PROJECT AT THIS INTERSECTION IS |
| PLANNED TO BEGIN CONSTRUCTION WITHIN THE NEXT YEAR, THE |
| SCHEDULE MAY NOT COINCIDE WITH THE DEVELOPMENT OF THIS |
| PARCEL. WHAT CONTINGENCY PLANS HAVE BEEN MADE IN THE |
| EVENT CONSTRUCTION OF THIS PARCEL PROCEEDS BEFORE THE |
| CITY'S PLANNED UTILITY CONSTRUCTION AND INTERSECTION |
| IMPROVEMENTS? |
| |
| THE DRIVEWAY ON GEORGIA AVENUE IS CENTERED ON TWO |
| EXISTING POWER POLES. HAVE THE OWNERS OF THE POLES BEEN |
| CONTACTED TO DETERMINE IF THE POLES CAN BE RELOCATED? |
| |
| THERE IS ALSO AN EXISTING ABOVE GROUND VALVE LOCATED |
| JUST SOUTH OF THE DRIVEWAY. WILL THIS VALVE BE REMOVED |
| OR RELOCATED? IF THE LINE IS GOING TO BE ABANDONED, |
| PLEASE INDICATE THAT THE LINE WILL BE REMOVED. |
| |
| PLEASE REVISE THE SIDEWALK-DRIVEWAY CROSSINGS TO |
| INCLUDE DETECTABLE WARNINGS THAT MEET FLORIDA |
| ACCESSIBILITY CODE AND ADA GUIDELINES. |
| |
| THE PLANS SHOW AN EXISTING OVERHEAD UTILITY LINE |
| CROSSING OVER THE PROPOSED NORTHERN BUILDING |
| (PHARMACY). IS THE OVERHEAD LINE NOT IN AN EXISTING |
| EASEMENT? PLEASE VERIFY THAT THE VERTICAL CLEARANCE IS |
| SUFFICIENT FOR CONSTRUCTION OF THE BUILDING. |
| |
| PLEASE SHOW THE LOCATIONS OF THE BACKFLOW PREVENTERS |
| FOR THE PROPOSED WATER SERVICES. IF ANY OF THE |
| BUILDINGS ARE PROPOSED TO BE SPRINKLED, PLEASE SHOW THE |
| LOCATION OF THE FIRE LINES. |
| |
| ARE THE SANITARY SERVICE LINES PROPOSED TO TIE INTO |
| EXISTING LATERALS OR ARE NEW CONNECTIONS PROPOSED? |
| PLEASE NOTE THAT THE PIPE SIZE BETWEEN THE MAIN LINE |
| AND THE WYE SHOULD BE A MINIMUM SIZE OF 6-INCHES IN |
| DIAMETER. |
| |
| ENGINEERING DEPARTMENT APPLICATION E1407002 MUST BE |
| APPROVED PRIOR TO START OF CONSTRUCTION. |
| |