2014-09-23 07:06:29 | BUILDING PLAN REVIEW |
| PERMIT: 14080956 |
| ADD: 4201 GEORGIA AVE |
| CONT: JOHN ROSSI |
| TEL: (561)659-5505 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 1ST REVIEW |
| DATE: TUES. SEPT. 23/2014 |
| ACTION: DENIED |
| |
| DESCRIPTION OF WORK: NEW CONSTRUCTION THE BUILDING OF 2 |
| BUILDINGS ONE A PHARMACY, THE SECOND A WAREHOUSE. |
| |
| 1) PLEASE SUBMIT A PERMIT APPLICATION FOR BOTH |
| BUILDINGS FOR RECORD KEEPING PURPOSES. CALLING IN |
| INSPECTIONS WILL BE DIFFICULT AS WELL AS WHEN TIME TO |
| PRINT CERTIFICATES OF OCCUPANCY, WE CAN NOT PRINT TWO |
| CERTIFICATE OF OCCUPANCIES UNDER ONE PERMIT FOR TWO |
| DIFFERENT OCCUPANCIES.PLEASE SPLIT THE VALUE OF EACH |
| BUILDING ACCORDINGLY AND WE WILL ASSESS THE PERMIT FEES |
| FOR EACH BUILDING FOR PLANS REVIEW & INSPECTIONS. |
| 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION 107.2.1.4 THE BUILDING |
| OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL POLICY, |
| OTHER STANDARDS FOR PLANS AND SPECIFICATIONS, IN ORDER |
| TO PROVIDE CONFORMITY TO ITS RECORD RETENTION PROGRAM. |
| THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, |
| SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO |
| RECORDS MANAGEMENT. |
| |
| 2) 2010 FBC-B 1803.5.2 QUESTIONABLE SOIL. WHERE THE |
| CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL |
| IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO |
| THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING |
| OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A |
| GEOTECHNICAL INVESTIGATION BE CONDUCTED. 1803.6 |
| REPORTING. WHERE GEOTECHNICAL INVESTIGATIONS ARE |
| REQUIRED, A WRITTEN REPORT OF THE INVESTIGATIONS SHALL |
| BE SUBMITTED TO THE BUILDING OFFICIAL BY THE OWNER OR |
| AUTHORIZED AGENT AT THE TIME OF PERMIT APPLICATION. |
| |
| 3) PROVIDE ENERGY CALCULATIONS. 103.3 EXAMINATION OF |
| DOCUMENTS. THE CODE OFFICIAL SHALL EXAMINE OR CAUSE TO |
| BE EXAMINED THE ACCOMPANYING CONSTRUCTION DOCUMENTS AND |
| SHALL ASCERTAIN WHETHER THE CONSTRUCTION INDICATED AND |
| DESCRIBED IS IN ACCORDANCE WITH THE REQUIREMENTS OF |
| THIS CODE AND OTHER PERTINENT LAWS OR ORDINANCES. |
| |
| 103.2.2 DETAILS REQUIRED. CONSTRUCTION DOCUMENTS SHALL |
| BE DRAWN TO SCALE UPON SUITABLE MATERIAL. CONSTRUCTION |
| DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE |
| THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED, |
| AND SHOW IN SUFFICIENT DETAIL PERTINENT DATA AND |
| FEATURES OF THE BUILDING, SYSTEMS AND EQUIPMENT AS |
| HEREIN GOVERNED. DETAILS SHALL INCLUDE, BUT ARE NOT |
| LIMITED TO, AS APPLICABLE, INSULATION MATERIALS AND |
| THEIR R-VALUES; FENESTRATION U-FACTORS AND SHGCS; |
| AREA-WEIGHTED U-FACTOR AND SHGC CALCULATIONS; |
| MECHANICAL SYSTEM DESIGN CRITERIA; MECHANICAL AND |
| SERVICE WATER HEATING SYSTEM AND EQUIPMENT TYPES, SIZES |
| AND EFFICIENCIES; ECONOMIZER DESCRIPTION; EQUIPMENT AND |
| SYSTEMS CONTROLS; FAN MOTOR HORSEPOWER (HP) AND |
| CONTROLS; DUCT SEALING, DUCT AND PIPE INSULATION AND |
| LOCATION; LIGHTING FIXTURE SCHEDULE WITH WATTAGE AND |
| CONTROL NARRATIVE; AND AIR SEALING DETAILS. |
| |
| 4) PRODUCT APPROVALS NOTE IF THEY ARE FOR BOTH |
| BUILDINGS OR IF FOR A PARTICULAR BUILDING WHICH |
| BUILDING, SINCE THE PLANS AND PRODUCT APPROVALS ARE |
| SUBMITTED AS ONE PACKAGE. 107.2.1.3 ADDITIONAL |
| INFORMATION IS REQUIRED. |
| |
| 5) BOTH BUILDINGS THE PRESSURES ARE IN VULT, PLEASE |
| ALSO SHOW VASD SINCE THE PRODUCT APPROVALS ARE TESTED |
| IN VASD. 2010 FBC-B 1609.3.1 WIND SPEED CONVERSION. |
| WHEN REQUIRED, ULTIMATE DESIGN WIND SPEEDS OF FIGURE |
| 1609A, B AND C SHALL BE CONVERTED TO NOMINAL DESIGN |
| WIND SPEEDS, VASD, USING TABLE 1609.3.1 OR EQUATION |
| 16-32. PRODUCT APPROVALS NOT REVIEWED, PRESSURES NOT IN |
| VASD. |
| |
| 6) MISSING: 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.41 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| WILL REQUIRE PRODUCT APPROVALS: |
| (31) (D) ROOFING PRODUCTS AND ASSEMBLIES ONLY PAGE |
| 13-0129.16 WAS SUBMITTED/ NOTE WILL REQUIRE ENHANCED |
| FASTENING, LIMITATION #7. |
| (G) PRE-ENGINEERED A/C STANDS |
| |
| 7) PLEASE PROVIDE WIND DESIGN FOR A/C CONDENSOR |
| SCREENING AND FRAME, AND ATTACHMENT TO STRUCTURE, |
| MWFRS. 2010 EITHER 3105.4.2.1 OR 3105.4.2.2. |
| |
| 8) SHEET A-3. PLEASE PROVIDE COMPLIANCE WITH THE 2010 |
| FBC-B 1509.6 EQUIPMENT AND APPLIANCES ON ROOFS OR |
| ELEVATED STRUCTURES. |
| WHERE EQUIPMENT AND APPLIANCES REQUIRING ACCESS ARE |
| INSTALLED ON ROOFS OR ELEVATED STRUCTURES AT A HEIGHT |
| EXCEEDING 16 FEET (4877 MM), SUCH ACCESS SHALL BE |
| PROVIDED BY A PERMANENT APPROVED MEANS OF ACCESS, THE |
| EXTENT OF WHICH SHALL BE FROM GRADE OR FLOOR LEVEL TO |
| THE EQUIPMENT AND APPLIANCES? LEVEL SERVICE SPACE. SUCH |
| ACCESS SHALL NOT REQUIRE CLIMBING OVER OBSTRUCTIONS |
| GREATER THAN 30 INCHES (762 MM) HIGH OR WALKING ON |
| ROOFS HAVING A SLOPE GREATER THAN 4 UNITS VERTICAL IN |
| 12 UNITS HORIZONTAL (33-PERCENT SLOPE). |
| PERMANENT LADDERS INSTALLED TO PROVIDE THE REQUIRED |
| ACCESS SHALL COMPLY WITH THE FOLLOWING MINIMUM DESIGN |
| CRITERIA: |
| 1. THE SIDE RAILING SHALL EXTEND ABOVE THE PARAPET OR |
| ROOF EDGE NOT LESS THAN 30 INCHES (762 MM). |
| 2. LADDERS SHALL HAVE RUNG SPACING NOT TO EXCEED 14 |
| INCHES (356 MM) ON CENTER. |
| 3. LADDERS SHALL HAVE A TOE SPACING NOT LESS THAN 6 |
| INCHES (152 MM) DEEP. |
| 4. THERE SHALL BE A MINIMUM OF 18 INCHES (457 MM) |
| BETWEEN RAILS. |
| 5. RUNGS SHALL HAVE A MINIMUM 0.75-INCH (19 MM) |
| DIAMETER AND BE CAPABLE OF WITHSTANDING A 300-POUND |
| (136.1 KG) LOAD. |
| 6. LADDERS OVER 30 FEET (9144 MM) IN HEIGHT SHALL BE |
| PROVIDED WITH OFFSET SECTIONS AND LANDINGS CAPABLE OF |
| WITHSTANDING 100 POUNDS |
| PER SQUARE FOOT. |
| 7. LADDERS SHALL BE PROTECTED AGAINST CORROSION BY |
| APPROVED MEANS. CATWALKS INSTALLED TO PROVIDE THE |
| REQUIRED ACCESS SHALL BE NOT L |
| LESS THAN 24 INCHES (610 MM) WIDE AND SHALL HAVE |
| RAILINGS AS REQUIRED FOR SERVICE PLATFORMS. |
| |
| NEW PHARMACY BUILDING: |
| |
| 9) LIFE SAFETY SHEET LS-1 PLEASE REVIEW THE 2010 FBC-B |
| TABLE 1004.1.1 FOR 1ST FLOOR MERCANTILE OCCUPANT LOAD |
| IS 30 SQ FT / OCCUPANT GROSS. |
| |
| 10) SHEET A3 PLEASE PROVIDE MANUFACTURERS SPEC FOR |
| ALUMINUM SUN SCREENS, AND THE INSTALATION AND ANCHORING |
| TO STRUCTURE. 2010 FBC-B 1609. / 3105.5.1 LOADS. RIGID |
| AWNINGS AND CANOPY SHUTTERS SHALL BE DESIGNED TO RESIST |
| THE LOADS SET FORTH IN CHAPTER 16 OF THIS CODE EXCEPT |
| THAT STRUCTURES OR PARTS THEREOF WHICH ARE INTENDED TO |
| BE REMOVED OR REPOSITIONED DURING PERIODS OF HIGH WIND |
| VELOCITY SHALL BE DESIGNED IN THEIR OPEN OR EXTENDED |
| POSITION TO DESIGN PRESSURES BASED ON A BASIC WIND |
| SPEED OF MINIMUM 115 MPH, 3-SECOND WIND GUST WITH |
| APPLICABLE SHAPE FACTORS AND TO RESIST NOT LESS THAN 10 |
| PSF (478 PA) ROOF LIVE LOAD. |
| |
| 11) NEITHER SHEET A3 NOR A5 SHOW THE ACTUAL HEIGHT AND |
| LOCATION IN RELATION TO THE FINISH ROOF LEVEL 2010 |
| FBC-B 1503.4.2. |
| |
| 12) PLEASE ALSO SHOW COMPLIANCE WITH 1503.4.2.1 |
| OVERFLOW SCUPPERS BEING BETWEEN 2 TO 4 INCHES ABOVE THE |
| FINISH ROOF LINE. |
| |
| 13) SHEET A5 DOES NOT SHOW THE EXTERIOR WALL INSULATION |
| ABOVE THE CEILING, PLEASE SHOW COMPLIANCE WITH 2010 |
| FBC-ENERGY 502.3.5.2 UNVENTED DROPPED CEILING CAVITIES. |
| WHERE UNVENTED DROPPED CEILING CAVITIES OCCUR OVER |
| CONDITIONED SPACES THAT DO NOT HAVE AN AIR BARRIER |
| BETWEEN THE CONDITIONED AND UNCONDITIONED SPACE (SUCH |
| AS T-BAR CEILINGS), THEY SHALL BE COMPLETELY SEALED |
| FROM THE EXTERIOR ENVIRONMENT (AT THE ROOF PLANE) AND |
| ADJACENT SPACES BY A CONTINUOUS AIR BARRIER THAT IS |
| ALSO SEALED TO THE AIR BARRIER OF THE WALLS. IN THAT |
| CASE, THE ROOF ASSEMBLY SHALL CONSTITUTE BOTH THE UPPER |
| THERMAL ENVELOPE AND PRESSURE ENVELOPE OF THE BUILDING. |
| |
| 14) SHEET AS ALSO SHOWS ICYENE SPRAY INSULATION OF THE |
| BOTTOM OF THE ROOF DECK. PLEASE PROVIDE THE |
| MANUFACTURERS TEST REPORT AND COMPLIANCE WITH: 2010 |
| FBC-B 2603.4.1.6 ATTICS AND CRAWL SPACES. |
| WITHIN AN ATTIC OR CRAWL SPACE WHERE ENTRY IS MADE ONLY |
| FOR SERVICE OF UTILITIES, FOAM PLASTIC INSULATION SHALL |
| BE PROTECTED AGAINST IGNITION BY 11/2-INCH-THICK (38 |
| MM) MINERAL FIBER INSULATION; 1/4-INCH-THICK (6.4 MM) |
| WOOD STRUCTURAL PANEL, PARTICLEBOARD OR HARDBOARD; |
| 3/8-INCH (9.5 MM) GYPSUM WALLBOARD, CORROSION-RESISTANT |
| STEEL HAVING A BASE METAL THICKNESS OF 0.016 INCH (0.4 |
| MM) OR OTHER APPROVED MATERIAL INSTALLED IN SUCH A |
| MANNER THAT THE FOAM PLASTIC INSULATION IS NOT EXPOSED. |
| THE PROTECTIVE COVERING SHALL BE CONSISTENT WITH THE |
| REQUIREMENTS FOR THE TYPE OF CONSTRUCTION. |
| |
| WAREHOUSE |
| |
| 15) SHEET A3 SHOWS THE OFFICE WALLS TO BE INSULATED, A |
| CUT SECTION LABELED A-A/A-6 SHOWS THESE WALLS NOT GOING |
| FULL HEIGHT, NO INSULATION IS SHOWN IN THE FRAME WALLS, |
| NOR THE CEILING JOIST CEILING OR EXTERIOR WALL. THIS |
| DETAIL LACKS THE TYPE OF FRAMING, IF THE CEILING JOIST |
| ARE GOING TO HAVE LIVE LOADS ABOVE THE OFFICE SPACE |
| (MEZZANINE LEVEL). IF SO WHAT WILL THE DESIGN CRITERIA |
| BE 125 LIGHT OR 250 HEAVY 2010 FBC-B 1607.1. |
| 107.2.1.3 ADDITIONAL DATA. THE BUILDING OFFICIAL MAY |
| REQUIRE DETAILS, COMPUTATIONS, STRESS DIAGRAMS, AND |
| OTHER DATA NECESSARY TO DESCRIBE THE CONSTRUCTION OR |
| INSTALLATION AND THE BASIS OF CALCULATIONS. |
| |
| 16) PLEASE TAKE NOTE THE PLANS DO NOT INDICATE WHERE |
| THE INSULATION WILL BE LOCATED IN REGUARDS TO THE |
| CEILING JOIST. 2010 FBC-B ENERGY 502.2.1.2 CEILING |
| INSULATION. |
| |
| SHEET A4 PLEASE PROVIDE MANUFACTURERS SPEC FOR ALUMINUM |
| SUN SCREENS, AND THE INSTALATION AND ANCHORING TO |
| STRUCTURE. 2010 FBC-B 1609. / 3105.5.1 LOADS. RIGID |
| AWNINGS AND CANOPY SHUTTERS SHALL BE DESIGNED TO RESIST |
| THE LOADS SET FORTH IN CHAPTER 16 OF THIS CODE EXCEPT |
| THAT STRUCTURES OR PARTS THEREOF WHICH ARE INTENDED TO |
| BE REMOVED OR REPOSITIONED DURING PERIODS OF HIGH WIND |
| VELOCITY SHALL BE DESIGNED IN THEIR OPEN OR EXTENDED |
| POSITION TO DESIGN PRESSURES BASED ON A BASIC WIND |
| SPEED OF MINIMUM 115 MPH, 3-SECOND WIND GUST WITH |
| APPLICABLE SHAPE FACTORS AND TO RESIST NOT LESS THAN 10 |
| PSF (478 PA) ROOF LIVE LOAD. |
| |
| 17) SHEET A-6 SHOWS ICYENE SPRAY INSULATION OF THE |
| BOTTOM OF THE ROOF DECK. PLEASE PROVIDE THE |
| MANUFACTURERS TEST REPORT AND COMPLIANCE WITH: 2010 |
| FBC-B 2603.4.1.6 ATTICS AND CRAWL SPACES. |
| WITHIN AN ATTIC OR CRAWL SPACE WHERE ENTRY IS MADE ONLY |
| FOR SERVICE OF UTILITIES, FOAM PLASTIC INSULATION SHALL |
| BE PROTECTED AGAINST IGNITION BY 11/2-INCH-THICK (38 |
| MM) MINERAL FIBER INSULATION; 1/4-INCH-THICK (6.4 MM) |
| WOOD STRUCTURAL PANEL, PARTICLEBOARD OR HARDBOARD; |
| 3/8-INCH (9.5 MM) GYPSUM WALLBOARD, CORROSION-RESISTANT |
| STEEL HAVING A BASE METAL THICKNESS OF 0.016 INCH (0.4 |
| MM) OR OTHER APPROVED MATERIAL INSTALLED IN SUCH A |
| MANNER THAT THE FOAM PLASTIC INSULATION IS NOT EXPOSED. |
| THE PROTECTIVE COVERING SHALL BE CONSISTENT WITH THE |
| REQUIREMENTS FOR THE TYPE OF CONSTRUCTION. |
| INSULATION INSTALLED ON A SUSPENDED CEILING WITH |
| REMOVABLE CEILING TILES SHALL NOT BE CONSIDERED PART OF |
| THE MINIMUM THERMAL RESISTANCE OF THE ROOF INSULATION |
| UNLESS THE ROOF/CEILING CAVITY IS SEALED FROM THE |
| EXTERIOR ENVIRONMENT. |
| |
| 18) SHEET A-3. PLEASE PROVIDE COMPLIANCE WITH THE 2010 |
| FBC-B 1509.6 EQUIPMENT AND APPLIANCES ON ROOFS OR |
| ELEVATED STRUCTURES. |
| WHERE EQUIPMENT AND APPLIANCES REQUIRING ACCESS ARE |
| INSTALLED ON ROOFS OR ELEVATED STRUCTURES AT A HEIGHT |
| EXCEEDING 16 FEET (4877 MM), SUCH ACCESS SHALL BE |
| PROVIDED BY A PERMANENT APPROVED MEANS OF ACCESS, THE |
| EXTENT OF WHICH SHALL BE FROM GRADE OR FLOOR LEVEL TO |
| THE EQUIPMENT AND APPLIANCES? LEVEL SERVICE SPACE. SUCH |
| ACCESS SHALL NOT REQUIRE CLIMBING OVER OBSTRUCTIONS |
| GREATER THAN 30 INCHES (762 MM) HIGH OR WALKING ON |
| ROOFS HAVING A SLOPE GREATER THAN 4 UNITS VERTICAL IN |
| 12 UNITS HORIZONTAL (33-PERCENT SLOPE). |
| PERMANENT LADDERS INSTALLED TO PROVIDE THE REQUIRED |
| ACCESS SHALL COMPLY WITH THE FOLLOWING MINIMUM DESIGN |
| CRITERIA: |
| 1. THE SIDE RAILING SHALL EXTEND ABOVE THE PARAPET OR |
| ROOF EDGE NOT LESS THAN 30 INCHES (762 MM). |
| 2. LADDERS SHALL HAVE RUNG SPACING NOT TO EXCEED 14 |
| INCHES (356 MM) ON CENTER. |
| 3. LADDERS SHALL HAVE A TOE SPACING NOT LESS THAN 6 |
| INCHES (152 MM) DEEP. |
| 4. THERE SHALL BE A MINIMUM OF 18 INCHES (457 MM) |
| BETWEEN RAILS. |
| 5. RUNGS SHALL HAVE A MINIMUM 0.75-INCH (19 MM) |
| DIAMETER AND BE CAPABLE OF WITHSTANDING A 300-POUND |
| (136.1 KG) LOAD. |
| 6. LADDERS OVER 30 FEET (9144 MM) IN HEIGHT SHALL BE |
| PROVIDED WITH OFFSET SECTIONS AND LANDINGS CAPABLE OF |
| WITHSTANDING 100 POUNDS |
| PER SQUARE FOOT. |
| 7. LADDERS SHALL BE PROTECTED AGAINST CORROSION BY |
| APPROVED MEANS. CATWALKS INSTALLED TO PROVIDE THE |
| REQUIRED ACCESS SHALL BE NOT L |
| LESS THAN 24 INCHES (610 MM) WIDE AND SHALL HAVE |
| RAILINGS AS REQUIRED FOR SERVICE PLATFORMS. |
| |
| 19) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |