Plan Review Notes
Plan Review Notes For Permit 14080956
Permit Number 14080956
Review Stop B
Sequence Number 1
Notes
Date Text
2014-09-23 07:06:29BUILDING PLAN REVIEW
 PERMIT: 14080956
 ADD: 4201 GEORGIA AVE
 CONT: JOHN ROSSI
 TEL: (561)659-5505
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: TUES. SEPT. 23/2014
 ACTION: DENIED
  
 DESCRIPTION OF WORK: NEW CONSTRUCTION THE BUILDING OF 2
 BUILDINGS ONE A PHARMACY, THE SECOND A WAREHOUSE.
  
 1) PLEASE SUBMIT A PERMIT APPLICATION FOR BOTH
 BUILDINGS FOR RECORD KEEPING PURPOSES. CALLING IN
 INSPECTIONS WILL BE DIFFICULT AS WELL AS WHEN TIME TO
 PRINT CERTIFICATES OF OCCUPANCY, WE CAN NOT PRINT TWO
 CERTIFICATE OF OCCUPANCIES UNDER ONE PERMIT FOR TWO
 DIFFERENT OCCUPANCIES.PLEASE SPLIT THE VALUE OF EACH
 BUILDING ACCORDINGLY AND WE WILL ASSESS THE PERMIT FEES
 FOR EACH BUILDING FOR PLANS REVIEW & INSPECTIONS.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1.4 THE BUILDING
 OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL POLICY,
 OTHER STANDARDS FOR PLANS AND SPECIFICATIONS, IN ORDER
 TO PROVIDE CONFORMITY TO ITS RECORD RETENTION PROGRAM.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT.
  
 2) 2010 FBC-B 1803.5.2 QUESTIONABLE SOIL. WHERE THE
 CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL
 IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO
 THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED. 1803.6
 REPORTING. WHERE GEOTECHNICAL INVESTIGATIONS ARE
 REQUIRED, A WRITTEN REPORT OF THE INVESTIGATIONS SHALL
 BE SUBMITTED TO THE BUILDING OFFICIAL BY THE OWNER OR
 AUTHORIZED AGENT AT THE TIME OF PERMIT APPLICATION.
  
 3) PROVIDE ENERGY CALCULATIONS. 103.3 EXAMINATION OF
 DOCUMENTS. THE CODE OFFICIAL SHALL EXAMINE OR CAUSE TO
 BE EXAMINED THE ACCOMPANYING CONSTRUCTION DOCUMENTS AND
 SHALL ASCERTAIN WHETHER THE CONSTRUCTION INDICATED AND
 DESCRIBED IS IN ACCORDANCE WITH THE REQUIREMENTS OF
 THIS CODE AND OTHER PERTINENT LAWS OR ORDINANCES.
  
 103.2.2 DETAILS REQUIRED. CONSTRUCTION DOCUMENTS SHALL
 BE DRAWN TO SCALE UPON SUITABLE MATERIAL. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED,
 AND SHOW IN SUFFICIENT DETAIL PERTINENT DATA AND
 FEATURES OF THE BUILDING, SYSTEMS AND EQUIPMENT AS
 HEREIN GOVERNED. DETAILS SHALL INCLUDE, BUT ARE NOT
 LIMITED TO, AS APPLICABLE, INSULATION MATERIALS AND
 THEIR R-VALUES; FENESTRATION U-FACTORS AND SHGCS;
 AREA-WEIGHTED U-FACTOR AND SHGC CALCULATIONS;
 MECHANICAL SYSTEM DESIGN CRITERIA; MECHANICAL AND
 SERVICE WATER HEATING SYSTEM AND EQUIPMENT TYPES, SIZES
 AND EFFICIENCIES; ECONOMIZER DESCRIPTION; EQUIPMENT AND
 SYSTEMS CONTROLS; FAN MOTOR HORSEPOWER (HP) AND
 CONTROLS; DUCT SEALING, DUCT AND PIPE INSULATION AND
 LOCATION; LIGHTING FIXTURE SCHEDULE WITH WATTAGE AND
 CONTROL NARRATIVE; AND AIR SEALING DETAILS.
  
 4) PRODUCT APPROVALS NOTE IF THEY ARE FOR BOTH
 BUILDINGS OR IF FOR A PARTICULAR BUILDING WHICH
 BUILDING, SINCE THE PLANS AND PRODUCT APPROVALS ARE
 SUBMITTED AS ONE PACKAGE. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 5) BOTH BUILDINGS THE PRESSURES ARE IN VULT, PLEASE
 ALSO SHOW VASD SINCE THE PRODUCT APPROVALS ARE TESTED
 IN VASD. 2010 FBC-B 1609.3.1 WIND SPEED CONVERSION.
 WHEN REQUIRED, ULTIMATE DESIGN WIND SPEEDS OF FIGURE
 1609A, B AND C SHALL BE CONVERTED TO NOMINAL DESIGN
 WIND SPEEDS, VASD, USING TABLE 1609.3.1 OR EQUATION
 16-32. PRODUCT APPROVALS NOT REVIEWED, PRESSURES NOT IN
 VASD.
  
 6) MISSING: 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31) (D) ROOFING PRODUCTS AND ASSEMBLIES ONLY PAGE
 13-0129.16 WAS SUBMITTED/ NOTE WILL REQUIRE ENHANCED
 FASTENING, LIMITATION #7.
 (G) PRE-ENGINEERED A/C STANDS
  
 7) PLEASE PROVIDE WIND DESIGN FOR A/C CONDENSOR
 SCREENING AND FRAME, AND ATTACHMENT TO STRUCTURE,
 MWFRS. 2010 EITHER 3105.4.2.1 OR 3105.4.2.2.
  
 8) SHEET A-3. PLEASE PROVIDE COMPLIANCE WITH THE 2010
 FBC-B 1509.6 EQUIPMENT AND APPLIANCES ON ROOFS OR
 ELEVATED STRUCTURES.
 WHERE EQUIPMENT AND APPLIANCES REQUIRING ACCESS ARE
 INSTALLED ON ROOFS OR ELEVATED STRUCTURES AT A HEIGHT
 EXCEEDING 16 FEET (4877 MM), SUCH ACCESS SHALL BE
 PROVIDED BY A PERMANENT APPROVED MEANS OF ACCESS, THE
 EXTENT OF WHICH SHALL BE FROM GRADE OR FLOOR LEVEL TO
 THE EQUIPMENT AND APPLIANCES? LEVEL SERVICE SPACE. SUCH
 ACCESS SHALL NOT REQUIRE CLIMBING OVER OBSTRUCTIONS
 GREATER THAN 30 INCHES (762 MM) HIGH OR WALKING ON
 ROOFS HAVING A SLOPE GREATER THAN 4 UNITS VERTICAL IN
 12 UNITS HORIZONTAL (33-PERCENT SLOPE).
 PERMANENT LADDERS INSTALLED TO PROVIDE THE REQUIRED
 ACCESS SHALL COMPLY WITH THE FOLLOWING MINIMUM DESIGN
 CRITERIA:
 1. THE SIDE RAILING SHALL EXTEND ABOVE THE PARAPET OR
 ROOF EDGE NOT LESS THAN 30 INCHES (762 MM).
 2. LADDERS SHALL HAVE RUNG SPACING NOT TO EXCEED 14
 INCHES (356 MM) ON CENTER.
 3. LADDERS SHALL HAVE A TOE SPACING NOT LESS THAN 6
 INCHES (152 MM) DEEP.
 4. THERE SHALL BE A MINIMUM OF 18 INCHES (457 MM)
 BETWEEN RAILS.
 5. RUNGS SHALL HAVE A MINIMUM 0.75-INCH (19 MM)
 DIAMETER AND BE CAPABLE OF WITHSTANDING A 300-POUND
 (136.1 KG) LOAD.
 6. LADDERS OVER 30 FEET (9144 MM) IN HEIGHT SHALL BE
 PROVIDED WITH OFFSET SECTIONS AND LANDINGS CAPABLE OF
 WITHSTANDING 100 POUNDS
 PER SQUARE FOOT.
 7. LADDERS SHALL BE PROTECTED AGAINST CORROSION BY
 APPROVED MEANS. CATWALKS INSTALLED TO PROVIDE THE
 REQUIRED ACCESS SHALL BE NOT L
 LESS THAN 24 INCHES (610 MM) WIDE AND SHALL HAVE
 RAILINGS AS REQUIRED FOR SERVICE PLATFORMS.
  
 NEW PHARMACY BUILDING:
  
 9) LIFE SAFETY SHEET LS-1 PLEASE REVIEW THE 2010 FBC-B
 TABLE 1004.1.1 FOR 1ST FLOOR MERCANTILE OCCUPANT LOAD
 IS 30 SQ FT / OCCUPANT GROSS.
  
 10) SHEET A3 PLEASE PROVIDE MANUFACTURERS SPEC FOR
 ALUMINUM SUN SCREENS, AND THE INSTALATION AND ANCHORING
 TO STRUCTURE. 2010 FBC-B 1609. / 3105.5.1 LOADS. RIGID
 AWNINGS AND CANOPY SHUTTERS SHALL BE DESIGNED TO RESIST
 THE LOADS SET FORTH IN CHAPTER 16 OF THIS CODE EXCEPT
 THAT STRUCTURES OR PARTS THEREOF WHICH ARE INTENDED TO
 BE REMOVED OR REPOSITIONED DURING PERIODS OF HIGH WIND
 VELOCITY SHALL BE DESIGNED IN THEIR OPEN OR EXTENDED
 POSITION TO DESIGN PRESSURES BASED ON A BASIC WIND
 SPEED OF MINIMUM 115 MPH, 3-SECOND WIND GUST WITH
 APPLICABLE SHAPE FACTORS AND TO RESIST NOT LESS THAN 10
 PSF (478 PA) ROOF LIVE LOAD.
  
 11) NEITHER SHEET A3 NOR A5 SHOW THE ACTUAL HEIGHT AND
 LOCATION IN RELATION TO THE FINISH ROOF LEVEL 2010
 FBC-B 1503.4.2.
  
 12) PLEASE ALSO SHOW COMPLIANCE WITH 1503.4.2.1
 OVERFLOW SCUPPERS BEING BETWEEN 2 TO 4 INCHES ABOVE THE
 FINISH ROOF LINE.
  
 13) SHEET A5 DOES NOT SHOW THE EXTERIOR WALL INSULATION
 ABOVE THE CEILING, PLEASE SHOW COMPLIANCE WITH 2010
 FBC-ENERGY 502.3.5.2 UNVENTED DROPPED CEILING CAVITIES.
 WHERE UNVENTED DROPPED CEILING CAVITIES OCCUR OVER
 CONDITIONED SPACES THAT DO NOT HAVE AN AIR BARRIER
 BETWEEN THE CONDITIONED AND UNCONDITIONED SPACE (SUCH
 AS T-BAR CEILINGS), THEY SHALL BE COMPLETELY SEALED
 FROM THE EXTERIOR ENVIRONMENT (AT THE ROOF PLANE) AND
 ADJACENT SPACES BY A CONTINUOUS AIR BARRIER THAT IS
 ALSO SEALED TO THE AIR BARRIER OF THE WALLS. IN THAT
 CASE, THE ROOF ASSEMBLY SHALL CONSTITUTE BOTH THE UPPER
 THERMAL ENVELOPE AND PRESSURE ENVELOPE OF THE BUILDING.
  
 14) SHEET AS ALSO SHOWS ICYENE SPRAY INSULATION OF THE
 BOTTOM OF THE ROOF DECK. PLEASE PROVIDE THE
 MANUFACTURERS TEST REPORT AND COMPLIANCE WITH: 2010
 FBC-B 2603.4.1.6 ATTICS AND CRAWL SPACES.
 WITHIN AN ATTIC OR CRAWL SPACE WHERE ENTRY IS MADE ONLY
 FOR SERVICE OF UTILITIES, FOAM PLASTIC INSULATION SHALL
 BE PROTECTED AGAINST IGNITION BY 11/2-INCH-THICK (38
 MM) MINERAL FIBER INSULATION; 1/4-INCH-THICK (6.4 MM)
 WOOD STRUCTURAL PANEL, PARTICLEBOARD OR HARDBOARD;
 3/8-INCH (9.5 MM) GYPSUM WALLBOARD, CORROSION-RESISTANT
 STEEL HAVING A BASE METAL THICKNESS OF 0.016 INCH (0.4
 MM) OR OTHER APPROVED MATERIAL INSTALLED IN SUCH A
 MANNER THAT THE FOAM PLASTIC INSULATION IS NOT EXPOSED.
 THE PROTECTIVE COVERING SHALL BE CONSISTENT WITH THE
 REQUIREMENTS FOR THE TYPE OF CONSTRUCTION.
  
 WAREHOUSE
  
 15) SHEET A3 SHOWS THE OFFICE WALLS TO BE INSULATED, A
 CUT SECTION LABELED A-A/A-6 SHOWS THESE WALLS NOT GOING
 FULL HEIGHT, NO INSULATION IS SHOWN IN THE FRAME WALLS,
 NOR THE CEILING JOIST CEILING OR EXTERIOR WALL. THIS
 DETAIL LACKS THE TYPE OF FRAMING, IF THE CEILING JOIST
 ARE GOING TO HAVE LIVE LOADS ABOVE THE OFFICE SPACE
 (MEZZANINE LEVEL). IF SO WHAT WILL THE DESIGN CRITERIA
 BE 125 LIGHT OR 250 HEAVY 2010 FBC-B 1607.1.
 107.2.1.3 ADDITIONAL DATA. THE BUILDING OFFICIAL MAY
 REQUIRE DETAILS, COMPUTATIONS, STRESS DIAGRAMS, AND
 OTHER DATA NECESSARY TO DESCRIBE THE CONSTRUCTION OR
 INSTALLATION AND THE BASIS OF CALCULATIONS.
  
 16) PLEASE TAKE NOTE THE PLANS DO NOT INDICATE WHERE
 THE INSULATION WILL BE LOCATED IN REGUARDS TO THE
 CEILING JOIST. 2010 FBC-B ENERGY 502.2.1.2 CEILING
 INSULATION.
  
 SHEET A4 PLEASE PROVIDE MANUFACTURERS SPEC FOR ALUMINUM
 SUN SCREENS, AND THE INSTALATION AND ANCHORING TO
 STRUCTURE. 2010 FBC-B 1609. / 3105.5.1 LOADS. RIGID
 AWNINGS AND CANOPY SHUTTERS SHALL BE DESIGNED TO RESIST
 THE LOADS SET FORTH IN CHAPTER 16 OF THIS CODE EXCEPT
 THAT STRUCTURES OR PARTS THEREOF WHICH ARE INTENDED TO
 BE REMOVED OR REPOSITIONED DURING PERIODS OF HIGH WIND
 VELOCITY SHALL BE DESIGNED IN THEIR OPEN OR EXTENDED
 POSITION TO DESIGN PRESSURES BASED ON A BASIC WIND
 SPEED OF MINIMUM 115 MPH, 3-SECOND WIND GUST WITH
 APPLICABLE SHAPE FACTORS AND TO RESIST NOT LESS THAN 10
 PSF (478 PA) ROOF LIVE LOAD.
  
 17) SHEET A-6 SHOWS ICYENE SPRAY INSULATION OF THE
 BOTTOM OF THE ROOF DECK. PLEASE PROVIDE THE
 MANUFACTURERS TEST REPORT AND COMPLIANCE WITH: 2010
 FBC-B 2603.4.1.6 ATTICS AND CRAWL SPACES.
 WITHIN AN ATTIC OR CRAWL SPACE WHERE ENTRY IS MADE ONLY
 FOR SERVICE OF UTILITIES, FOAM PLASTIC INSULATION SHALL
 BE PROTECTED AGAINST IGNITION BY 11/2-INCH-THICK (38
 MM) MINERAL FIBER INSULATION; 1/4-INCH-THICK (6.4 MM)
 WOOD STRUCTURAL PANEL, PARTICLEBOARD OR HARDBOARD;
 3/8-INCH (9.5 MM) GYPSUM WALLBOARD, CORROSION-RESISTANT
 STEEL HAVING A BASE METAL THICKNESS OF 0.016 INCH (0.4
 MM) OR OTHER APPROVED MATERIAL INSTALLED IN SUCH A
 MANNER THAT THE FOAM PLASTIC INSULATION IS NOT EXPOSED.
 THE PROTECTIVE COVERING SHALL BE CONSISTENT WITH THE
 REQUIREMENTS FOR THE TYPE OF CONSTRUCTION.
 INSULATION INSTALLED ON A SUSPENDED CEILING WITH
 REMOVABLE CEILING TILES SHALL NOT BE CONSIDERED PART OF
 THE MINIMUM THERMAL RESISTANCE OF THE ROOF INSULATION
 UNLESS THE ROOF/CEILING CAVITY IS SEALED FROM THE
 EXTERIOR ENVIRONMENT.
  
 18) SHEET A-3. PLEASE PROVIDE COMPLIANCE WITH THE 2010
 FBC-B 1509.6 EQUIPMENT AND APPLIANCES ON ROOFS OR
 ELEVATED STRUCTURES.
 WHERE EQUIPMENT AND APPLIANCES REQUIRING ACCESS ARE
 INSTALLED ON ROOFS OR ELEVATED STRUCTURES AT A HEIGHT
 EXCEEDING 16 FEET (4877 MM), SUCH ACCESS SHALL BE
 PROVIDED BY A PERMANENT APPROVED MEANS OF ACCESS, THE
 EXTENT OF WHICH SHALL BE FROM GRADE OR FLOOR LEVEL TO
 THE EQUIPMENT AND APPLIANCES? LEVEL SERVICE SPACE. SUCH
 ACCESS SHALL NOT REQUIRE CLIMBING OVER OBSTRUCTIONS
 GREATER THAN 30 INCHES (762 MM) HIGH OR WALKING ON
 ROOFS HAVING A SLOPE GREATER THAN 4 UNITS VERTICAL IN
 12 UNITS HORIZONTAL (33-PERCENT SLOPE).
 PERMANENT LADDERS INSTALLED TO PROVIDE THE REQUIRED
 ACCESS SHALL COMPLY WITH THE FOLLOWING MINIMUM DESIGN
 CRITERIA:
 1. THE SIDE RAILING SHALL EXTEND ABOVE THE PARAPET OR
 ROOF EDGE NOT LESS THAN 30 INCHES (762 MM).
 2. LADDERS SHALL HAVE RUNG SPACING NOT TO EXCEED 14
 INCHES (356 MM) ON CENTER.
 3. LADDERS SHALL HAVE A TOE SPACING NOT LESS THAN 6
 INCHES (152 MM) DEEP.
 4. THERE SHALL BE A MINIMUM OF 18 INCHES (457 MM)
 BETWEEN RAILS.
 5. RUNGS SHALL HAVE A MINIMUM 0.75-INCH (19 MM)
 DIAMETER AND BE CAPABLE OF WITHSTANDING A 300-POUND
 (136.1 KG) LOAD.
 6. LADDERS OVER 30 FEET (9144 MM) IN HEIGHT SHALL BE
 PROVIDED WITH OFFSET SECTIONS AND LANDINGS CAPABLE OF
 WITHSTANDING 100 POUNDS
 PER SQUARE FOOT.
 7. LADDERS SHALL BE PROTECTED AGAINST CORROSION BY
 APPROVED MEANS. CATWALKS INSTALLED TO PROVIDE THE
 REQUIRED ACCESS SHALL BE NOT L
 LESS THAN 24 INCHES (610 MM) WIDE AND SHALL HAVE
 RAILINGS AS REQUIRED FOR SERVICE PLATFORMS.
  
 19) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]