2014-08-26 12:25:401) SUBMIT MANUFACTURER SPEC. SHEETS FOR THE TANKLESS
 WATER HEATER,RANGE,DRYER, POOL HEATER & FIREPLACE.
 APPLIANCES SHALL BE LISTED AND LABELED PER THE 2010 FGC
 SEC.301.3.
 2) SUBMIT A CLEAR AND LEGIBLE SURVEY SHOWING THE
 DISTANCE OF THE WATER FROM THE PROPERTY LINES ( SIDE &
 REAR)
 3) SUBMIT A GAS RISER DIAGRAM SHOWINGTHE LOCATION OF
 SHUTOFF VALVES AND SECOND STAGE REGULATORS AND THE
 LENGTHS OF THE SECTIONS OF PIPE. CITY WPB ADMIN. AMEND.
 TO 2010 FBC SEC.107.3.5.3. (12).
 4) SUBMIT A COPY OF THE APPROPRIATE TABLE FOR THE CSST
 PIPE FROM THE GAS CODE.SHOW THE CORRESPONDING EHD FOR
 THE CSST ON THE PLAN FROM THE APPROPRIATE GAS SIZING
 TABLE.
 5) INDICATE THE PSI FOR THE CSST SYSTEM.CITY OF WPB
 ADMIN. AMEND. TO 2010 FBC SEC.107.2.1.