Review Stop B
Sequence Number 1
Notes
Date Text
2014-08-22 14:30:47E-MAIL SENT:
 TO GEORGE,
  
 THE FLAT ROOF PRODUCT APPROVAL SUBMITTED NOA #
 13-0514.12 DOES NOT IDENTIFY WHICH SUB-SYSTEM IS BEING
 INSTALLED. THERE ARE INSULATED AND NON-INSULATES
 SUB-SYSTEMS. PLEASE PROVIDE WHICH SUB-SYSTEM IS TO BE
 INSTALLED. PLEASE NOTE THE REQUIRED PRESSURES IN ZONE #
 2 IS -63.6 AND ROOF ZONE # 3 -95.7. IF THE SUB-SYSTEM
 LIST GENERAL LIMITATION # 7 THEN A DESIGN PROFESSIONAL
 WILL CALCULATE THE FASTENING PATTERN USING RAS 117.
  
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER