2015-01-29 15:24:06 | 4TH REVIEW: FBC 2010 |
| |
| IN THIS RE-SUBMITTAL, THE APPLICANT HAS PROVIDED A DCA |
| PLAN MDS007344. THE DCA COVER LETTER WAS NOT PROVIDED, |
| AND THE PLANS DO NOT HAVE THE DCA STAMP ON THEM. I WAS |
| UNABLE TO LOCATE THE PLAN ON FLORIDABUILDING.ORG. IT IS |
| UNCLEAR HOW THIS PLAN RELATES TO THE INSIGNAI |
| PREVIOUSLY PROVIDED. |
| |
| THE PLAN SUBMITTED IS FOR EDUCATIONAL OCCUPANCY; |
| THEREFORE, THIS HAS BEEN REVIEWED FOR EDUCATIONAL USE |
| ONLY. PLEASE ADDRESS. NO INFORMATION WAS PROVIDED |
| REGARDING THE PROPOSED USE OF THIS STRUCTURE. ALTHOUGH |
| APPLICATION STATES THIS IS "EXISTING" IT IS NOT |
| CONSIDERED "EXISTING" IF A PERMIT WAS NOT OBTAINED. IT |
| APPEARS THAT THIS WAS INSTALLED AFTER 2012. |
| |
| FROM PREVIOUS LISTS, BE ADVISED THAT THE FOUNDATION |
| PLAN DOES NOT COMPLY WITH FBC R403.1.4 MINIMUM DEPTH. |
| ALL EXTERIOR FOOTINGS SHALL BE PLACED AT LEAST 12 |
| INCHES (305 MM) BELOW THE UNDISTURBED GROUND SURFACE. |
| NO ADDITIONAL INFORMATION WAS PROVIDED. |
| |
| ELECTRICAL IS SHOWN ON THE MODULAR PLAN, AS WELL AS AN |
| OPTIONAL BATHROOM, BUT NO INFORMATION PROVIDED |
| REGARDING ELECTRICAL CONNECTION OR PLUMBING CONNECTION |
| FOR REVIEW. PLANS WILL BE ROUTED FOR ELECTRICAL AND |
| PLUMBING REVIEWS AFTER THIS INFORMATION IS SUBMITTED. |
| |
| FROM PREVIOUS THREE REVIEWS, FBC 109.3 BUILDING PERMIT |
| VALUATION. FOR PERMITTING PURPOSES, VALUATION OF |
| BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE |
| TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL, |
| INTERIOR FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND |
| DESIGN FEES, MARKETING COSTS, OVERHEAD AND PROFIT; |
| EXCLUDING ONLY LAND VALUE. VALUATION REFERENCES MAY |
| INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL |
| CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT, |
| MEANS, ETC.), AS PUBLISHED BY INTERNATIONAL CODE |
| CONGRESS. FINAL BUILDING PERMIT VALUATION SHALL BE SET |
| BY THE BUILDING OFFICIAL. |
| |
| NO IMPACT PROTECTION SHOWN FOR THE MODULAR, PLEASE |
| ADDRESS FBC 2010 RESIDENTIAL 301.2.1.2, FBC 1609.1.4. |
| (OCCUPANCY CLASSIFICATION HAS NOT BEEN DETERMINED.) IF |
| REMOVABLE SHUTTERS ARE PROPOSED, PROVIDE PRODUCT |
| APPROVALS AND THE SAMPLE INSTALLATION SCHEDULE (OR ALL |
| INFORMATION IN ANOTHER FORMAT): |
| |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/SCHEDULE_FOR_INSTALLATION.PDF |
| |
| WHEN RESUBMITTING, PLEASE PROVIDE A RESPONSE LETTER |
| STATING HOW EACH ITEM WAS ADDRESSED (THIS MAY BE DONE |
| BY CONTRACTOR). ENGINEER IS TO ACKNOWLEDGE RECEIPT OF |
| THE STRUCTURAL COMMENT. |
| |
| SAMANTHA M. HILL |
| BUILDING PLANS EXAMINER |
| 561-805-6724 |
| [email protected] |
| |