Plan Review Notes
Plan Review Notes For Permit 14080903
Permit Number 14080903
Review Stop B
Sequence Number 4
Notes
Date Text
2015-01-29 15:24:064TH REVIEW: FBC 2010
  
 IN THIS RE-SUBMITTAL, THE APPLICANT HAS PROVIDED A DCA
 PLAN MDS007344. THE DCA COVER LETTER WAS NOT PROVIDED,
 AND THE PLANS DO NOT HAVE THE DCA STAMP ON THEM. I WAS
 UNABLE TO LOCATE THE PLAN ON FLORIDABUILDING.ORG. IT IS
 UNCLEAR HOW THIS PLAN RELATES TO THE INSIGNAI
 PREVIOUSLY PROVIDED.
  
 THE PLAN SUBMITTED IS FOR EDUCATIONAL OCCUPANCY;
 THEREFORE, THIS HAS BEEN REVIEWED FOR EDUCATIONAL USE
 ONLY. PLEASE ADDRESS. NO INFORMATION WAS PROVIDED
 REGARDING THE PROPOSED USE OF THIS STRUCTURE. ALTHOUGH
 APPLICATION STATES THIS IS "EXISTING" IT IS NOT
 CONSIDERED "EXISTING" IF A PERMIT WAS NOT OBTAINED. IT
 APPEARS THAT THIS WAS INSTALLED AFTER 2012.
  
 FROM PREVIOUS LISTS, BE ADVISED THAT THE FOUNDATION
 PLAN DOES NOT COMPLY WITH FBC R403.1.4 MINIMUM DEPTH.
 ALL EXTERIOR FOOTINGS SHALL BE PLACED AT LEAST 12
 INCHES (305 MM) BELOW THE UNDISTURBED GROUND SURFACE.
 NO ADDITIONAL INFORMATION WAS PROVIDED.
  
 ELECTRICAL IS SHOWN ON THE MODULAR PLAN, AS WELL AS AN
 OPTIONAL BATHROOM, BUT NO INFORMATION PROVIDED
 REGARDING ELECTRICAL CONNECTION OR PLUMBING CONNECTION
 FOR REVIEW. PLANS WILL BE ROUTED FOR ELECTRICAL AND
 PLUMBING REVIEWS AFTER THIS INFORMATION IS SUBMITTED.
  
 FROM PREVIOUS THREE REVIEWS, FBC 109.3 BUILDING PERMIT
 VALUATION. FOR PERMITTING PURPOSES, VALUATION OF
 BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE
 TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL,
 INTERIOR FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND
 DESIGN FEES, MARKETING COSTS, OVERHEAD AND PROFIT;
 EXCLUDING ONLY LAND VALUE. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT,
 MEANS, ETC.), AS PUBLISHED BY INTERNATIONAL CODE
 CONGRESS. FINAL BUILDING PERMIT VALUATION SHALL BE SET
 BY THE BUILDING OFFICIAL.
  
 NO IMPACT PROTECTION SHOWN FOR THE MODULAR, PLEASE
 ADDRESS FBC 2010 RESIDENTIAL 301.2.1.2, FBC 1609.1.4.
 (OCCUPANCY CLASSIFICATION HAS NOT BEEN DETERMINED.) IF
 REMOVABLE SHUTTERS ARE PROPOSED, PROVIDE PRODUCT
 APPROVALS AND THE SAMPLE INSTALLATION SCHEDULE (OR ALL
 INFORMATION IN ANOTHER FORMAT):
  
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/SCHEDULE_FOR_INSTALLATION.PDF
  
 WHEN RESUBMITTING, PLEASE PROVIDE A RESPONSE LETTER
 STATING HOW EACH ITEM WAS ADDRESSED (THIS MAY BE DONE
 BY CONTRACTOR). ENGINEER IS TO ACKNOWLEDGE RECEIPT OF
 THE STRUCTURAL COMMENT.
  
 SAMANTHA M. HILL
 BUILDING PLANS EXAMINER
 561-805-6724
 [email protected]
  