Plan Review Notes
Plan Review Notes For Permit 14080903
Permit Number 14080903
Review Stop P
Sequence Number 1
Notes
Date Text
2015-03-01 08:14:551)THE OCCUPANCY NOTED ON THE PLANS IS SHOWN AS
 EDUCATIONAL. TABLE 403.1 OF THE FL. PLUMBING CODE
 REQUIRES SEPARATE FACILITIES FOR THE MALES AND FEMALES.
 A MINIMUM OF ONE WATER CLOSET AND ONE LAVATORY SHALL BE
 PROVIDED FOR THE MALES AND ALSO THE FEMALES. A SERVICE
 SINK IS ALSO REQUIRED AND A DRINKING FOUNTAIN.
 2) A MINIMUM OF TWO DRINKING FOUNTAINS SHALL BE
 SUPPLIED IN ACCORDANCE WITH THE 2010 FL. ACCESSIBILITY
 CODE SEC. 211.2
 3) THE BUILDING SHALL COMPLY WITH FL. STATUTE 553.415
 AND SECTION 428 OF THE 2010 FL. BUILDING CODE. APPROVED
 PLANS AND SPECIFICATIONS SHALL BE EVIDENCED BY A LETTER
 OF CERTIFICATION FROM THE AGENCY AUTHORIZED TO PERFORM
 INSPECTIONS OF OR REVIEW PLANS FOR MANUFACTURED
 BUILDINGS AS PROVIDED IN FL. ADMIN. RULE 9B-1 PER THE
 2010 FBC SEC.428.2, 428.4.2.
 4) SHT. A1 SHOWS A CITY WATER CONNECTION TO THE TRAILER
 AND THERE IS ALSO AN 8 1/2' X 11' DRAWING STAPLED TO
 THE PLAN SHOWING THE SOURCE OF WATER BEING A RAIN
 BARREL. CLARIFY. IF A RAIN BARREL WILL BE THE WATER
 SOURCE, SUBMIT A COMPLETE PIPNG PLAN INCLUDING THE PUMP
 SHOWING HOW THE WATER WILL BE PIPED TO THE TRAILER AND
 HOW THE PRESSURE WILL BE MAINTAINED. WPB AMEND. TO 2010
 FBC SEC. 107.2.1.
 5) ONLY POTABLE WATER SHALL BE SUPPLIED TO PLUMBING
 FIXTURES THAT PROVIDE WATER FOR DRINKING , BATHING, OR
 CULINARY PURPOSES PER THE 2010 FPC SEC. 602.2. SIGNS
 SHALL BE POSTED AT ANY FIXTURE UTILIZING NON-POTABLE
 WATER THAT THE WATER IS NON-POTABLE AND NOT FOR DRINING
 PURPOSES.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  