2015-03-01 08:14:55 | 1)THE OCCUPANCY NOTED ON THE PLANS IS SHOWN AS |
| EDUCATIONAL. TABLE 403.1 OF THE FL. PLUMBING CODE |
| REQUIRES SEPARATE FACILITIES FOR THE MALES AND FEMALES. |
| A MINIMUM OF ONE WATER CLOSET AND ONE LAVATORY SHALL BE |
| PROVIDED FOR THE MALES AND ALSO THE FEMALES. A SERVICE |
| SINK IS ALSO REQUIRED AND A DRINKING FOUNTAIN. |
| 2) A MINIMUM OF TWO DRINKING FOUNTAINS SHALL BE |
| SUPPLIED IN ACCORDANCE WITH THE 2010 FL. ACCESSIBILITY |
| CODE SEC. 211.2 |
| 3) THE BUILDING SHALL COMPLY WITH FL. STATUTE 553.415 |
| AND SECTION 428 OF THE 2010 FL. BUILDING CODE. APPROVED |
| PLANS AND SPECIFICATIONS SHALL BE EVIDENCED BY A LETTER |
| OF CERTIFICATION FROM THE AGENCY AUTHORIZED TO PERFORM |
| INSPECTIONS OF OR REVIEW PLANS FOR MANUFACTURED |
| BUILDINGS AS PROVIDED IN FL. ADMIN. RULE 9B-1 PER THE |
| 2010 FBC SEC.428.2, 428.4.2. |
| 4) SHT. A1 SHOWS A CITY WATER CONNECTION TO THE TRAILER |
| AND THERE IS ALSO AN 8 1/2' X 11' DRAWING STAPLED TO |
| THE PLAN SHOWING THE SOURCE OF WATER BEING A RAIN |
| BARREL. CLARIFY. IF A RAIN BARREL WILL BE THE WATER |
| SOURCE, SUBMIT A COMPLETE PIPNG PLAN INCLUDING THE PUMP |
| SHOWING HOW THE WATER WILL BE PIPED TO THE TRAILER AND |
| HOW THE PRESSURE WILL BE MAINTAINED. WPB AMEND. TO 2010 |
| FBC SEC. 107.2.1. |
| 5) ONLY POTABLE WATER SHALL BE SUPPLIED TO PLUMBING |
| FIXTURES THAT PROVIDE WATER FOR DRINKING , BATHING, OR |
| CULINARY PURPOSES PER THE 2010 FPC SEC. 602.2. SIGNS |
| SHALL BE POSTED AT ANY FIXTURE UTILIZING NON-POTABLE |
| WATER THAT THE WATER IS NON-POTABLE AND NOT FOR DRINING |
| PURPOSES. |
| |
| PLUMBING PLAN REVIEW |