Plan Review Notes
Plan Review Notes For Permit 14080872
Permit Number 14080872
Review Stop E
Sequence Number 1
Notes
Date Text
2014-09-22 18:39:07APPROVED WITH EXCEPTION.
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S).
  
 1) NEC 210.8 (A) (1)-(8) - GROUND-FAULT
 CIRCUIT-INTERRUPTER PROTECTION REQUIRED. PROVIDE GFCI
 PROTECTION IN THE GARAGE, UTILITY ROOM AND RECEPTACLES
 SERVING THE KITCHEN COUNTERTOPS.
  
 2) NEC 210.70 PROVIDE A SWITCH CONTROLLED LIGHTING
 OUTLET IN EACH ATTIC SPACE.