Plan Review Notes For Permit 14080872 |
Permit Number |
14080872 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-09-22 18:39:07 | APPROVED WITH EXCEPTION. | | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO | | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO | | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE | | ASSESSMENT OF RE-INSPECTION FEE(S). | | | | 1) NEC 210.8 (A) (1)-(8) - GROUND-FAULT | | CIRCUIT-INTERRUPTER PROTECTION REQUIRED. PROVIDE GFCI | | PROTECTION IN THE GARAGE, UTILITY ROOM AND RECEPTACLES | | SERVING THE KITCHEN COUNTERTOPS. | | | | 2) NEC 210.70 PROVIDE A SWITCH CONTROLLED LIGHTING | | OUTLET IN EACH ATTIC SPACE. |
|