Date |
Text |
2014-08-20 11:03:40 | DATE: 8/20/2014 |
| PROJECT: |
| PERMIT#: |
| CODE: 2008 EDITION OF THE NEC |
| 2010 EDITION OF THE FBC |
| 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| |
| 1ST ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| 1) A MAIN SERVICE DISCONNECTING MEANS IS REQUIRED. |
| INDICATE THE LOCATION OF THE SERVICE ENTRANCE MAIN OCPD |
| DISCONNECTING MEANS. NEC 230.70 |
| |
| 2) A PANEL SCHEDULE IS REQUIRED FOR THE SERVICE |
| ENTRANCE PANEL TO IDENTIFY THE BRANCH CIRCUIT(S) FROM |
| THE MAIN SERVICE PANEL TO FEED THE HOUSE PANEL AND THE |
| SUB-PANEL. REVISE THE PLAN TO COMPLY. |
| |
| 3) THE #2 WIRE FEEDING THE HOUSE PANEL INDICATED AS |
| 150AMP ARE UNDERSIZED. 310.15(B)(6) |
| REVISE THE RISER DIAGRAM TO COMPLY. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT |
| /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM |
| ITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| SHEETS FOR COMPARATIVE REVIEW. |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |