Plan Review Notes
Plan Review Notes For Permit 14080814
Permit Number 14080814
Review Stop E
Sequence Number 1
Notes
Date Text
2014-08-19 13:19:50DATE: 8/19/2014
 PROJECT: NORTHWOOD
 PERMIT#: 14080814
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 WHEN ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL
 314.3 AND 314.3.1
 PROVIDE DUAL VOLTAGE INTERCONNECTED SMOKE DETECTORS PER
 THE FBC 314, 315.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  