Plan Review Notes For Permit 14080805 |
Permit Number |
14080805 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-09-06 10:35:43 | PLAN DENIED | | | | 1) REFER TO SECTION 503.2.4.4 SHUTOFF DAMPER CONTROLS | | 2010 FLORIDA ENERGY CODE. | | 2) PROVIDE DETAIL FROM A ENGINEER ON THE MOUNTING OF | | THE CONDENSER TO THE WALL. PER SECTION 301.12 WIND | | RESISTANCE | | 2010 FBC (M) CUT SHEET WAS NOT PROVIDED. | | 3) REFER TO SECTION 606.2.1 SUPPLY AIR SYSTEM 2010 FBC | | (M) | | 4) PROVIDE NOA ON WALL MOUNTED LOUVER FOR FRESH AIR. | | 5) PROVIDE A SIGNATURE AND LIC. NUMBER OF WHO EVER DREW | | THE PLANS | | PER SECTION 107 FBC 2010 | | | | PLAN REVIEW BY HAROLD MOSER | | [email protected] | | OFFICE 561-805-6732 | | FAX 561-805-6676 |
|