2014-09-06 10:35:43PLAN DENIED
  
 1) REFER TO SECTION 503.2.4.4 SHUTOFF DAMPER CONTROLS
 2010 FLORIDA ENERGY CODE.
 2) PROVIDE DETAIL FROM A ENGINEER ON THE MOUNTING OF
 THE CONDENSER TO THE WALL. PER SECTION 301.12 WIND
 RESISTANCE
 2010 FBC (M) CUT SHEET WAS NOT PROVIDED.
 3) REFER TO SECTION 606.2.1 SUPPLY AIR SYSTEM 2010 FBC
 (M)
 4) PROVIDE NOA ON WALL MOUNTED LOUVER FOR FRESH AIR.
 5) PROVIDE A SIGNATURE AND LIC. NUMBER OF WHO EVER DREW
 THE PLANS
 PER SECTION 107 FBC 2010
  