2014-08-26 17:03:06 | BUILDING PLAN REVIEW |
| PERMIT: 14080805 |
| ADD: 201 NARCISSUS AVE. |
| CONT: URBAN BUILDING CONCEPT |
| TEL: (561)727-8343 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: WED. AUGUST 27/2014 |
| ACTION: DENIED |
| |
| 1) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.41 COMPONENTS & CLADDING |
| |
| FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| (B) WINDOWS |
| (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| LOUVERS, |
| |
| 2) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 3A) THE PLANS DO NOT INDICATE IF THIS ENCLOSED SPACE IS |
| TO BE AIR CONDITIONED OR NATURALLY VENTILATED? 2010 |
| FBC-B |
| 1203.4 NATURAL VENTILATION. |
| NATURAL VENTILATION OF AN OCCUPIED SPACE SHALL BE |
| THROUGH WINDOWS, DOORS, LOUVERS OR OTHER OPENINGS TO |
| THE OUTDOORS. THE OPERATING MECHANISM FOR SUCH OPENINGS |
| SHALL BE PROVIDED WITH READY ACCESS SO THAT THE |
| OPENINGS ARE READILY CONTROLLABLE BY THE BUILDING |
| OCCUPANTS. |
| 1203.4.1 VENTILATION AREA REQUIRED. THE MINIMUM |
| OPENABLE AREA TO THE OUTDOORS SHALL BE 4 PERCENT OF THE |
| FLOOR AREA BEING VENTILATED. |
| |
| 3B) IF THIS SPACE IS TO BE AIR CONDITIONED PLEASE |
| PROVIDE THE MINIMUM AMOUNTS OF INSULATION REQUIRED TO |
| MEET THE REQUIREMENT IN THE 2010 FBC-ENERGY CODE |
| 502.2.1.2 CEILING INSULATION & 502.2.2.1.1. WALL |
| INSULATION ABOVE GRADE. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |