Plan Review Notes
Plan Review Notes For Permit 14080805
Permit Number 14080805
Review Stop B
Sequence Number 1
Notes
Date Text
2014-08-26 17:03:06BUILDING PLAN REVIEW
 PERMIT: 14080805
 ADD: 201 NARCISSUS AVE.
 CONT: URBAN BUILDING CONCEPT
 TEL: (561)727-8343
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. AUGUST 27/2014
 ACTION: DENIED
  
 1) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS,
  
 2) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 3A) THE PLANS DO NOT INDICATE IF THIS ENCLOSED SPACE IS
 TO BE AIR CONDITIONED OR NATURALLY VENTILATED? 2010
 FBC-B
 1203.4 NATURAL VENTILATION.
 NATURAL VENTILATION OF AN OCCUPIED SPACE SHALL BE
 THROUGH WINDOWS, DOORS, LOUVERS OR OTHER OPENINGS TO
 THE OUTDOORS. THE OPERATING MECHANISM FOR SUCH OPENINGS
 SHALL BE PROVIDED WITH READY ACCESS SO THAT THE
 OPENINGS ARE READILY CONTROLLABLE BY THE BUILDING
 OCCUPANTS.
 1203.4.1 VENTILATION AREA REQUIRED. THE MINIMUM
 OPENABLE AREA TO THE OUTDOORS SHALL BE 4 PERCENT OF THE
 FLOOR AREA BEING VENTILATED.
  
 3B) IF THIS SPACE IS TO BE AIR CONDITIONED PLEASE
 PROVIDE THE MINIMUM AMOUNTS OF INSULATION REQUIRED TO
 MEET THE REQUIREMENT IN THE 2010 FBC-ENERGY CODE
 502.2.1.2 CEILING INSULATION & 502.2.2.1.1. WALL
 INSULATION ABOVE GRADE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]