2014-08-22 08:34:47 | DATE: 8/19/2014 |
| PROJECT: HOPKINS MARINE |
| PERMIT#: 14050989, REVISION TRACKING #14080802 |
| CODE: 2008 EDITION OF THE NEC |
| 2010 EDITION OF THE FBC |
| 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| |
| 2ND ELECTRICAL PLAN REVIEW, REVISION TRACKING #14080802 |
| ACTION: DENIED |
| |
| 1)EMERGENCY ILLUMINATION SHALL INCLUDE ALL REQUIRED |
| MEANS OF EGRESS LIGHTING, ILLUMINATED EXIT SIGNS, AND |
| ALL OTHER LIGHTS SPECIFIED AS NECESSARY TO PROVIDE |
| REQUIRED ILLUMINATION. EMERGENCY LIGHTING SYSTEMS SHALL |
| BE DESIGNED AND INSTALLED SO THAT THE FAILURE OF ANY |
| INDIVIDUAL LIGHTING ELEMENT, SUCH AS THE BURNING OUT OF |
| A LAMP, CANNOT LEAVE IN TOTAL DARKNESS ANY SPACE THAT |
| REQUIRES EMERGENCY ILLUMINATION. NEC 700.16 |
| REVISE PLANS TO INDICATE COMPLIANCE WITH NEC 700.16 |
| |
| 2) PROVIDE WIND LOAD CALCULATIONS FOR POLE LIGHT IN THE |
| PARKING LOT. |
| |
| 3) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY |
| MANUFACTURERS EQUIPMENT SUBMITTALS, PLANS, AND SHOP |
| DRAWINGS AS REQUIRED FOR CCTV, DATA/COM, NETWORK, |
| AUDIO/VIDEO, AND SIGNAGE. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT |
| /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM |
| ITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| SHEETS FOR COMPARATIVE REVIEW. |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |