2014-08-19 13:52:31 | DATE: 8/19/2014 |
| PROJECT: POTTER |
| PERMIT#: 14080799 |
| CODE: 2008 EDITION OF THE NEC |
| 2010 EDITION OF THE FBC |
| 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| |
| 1ST ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| 1) THE GROUNDING ELECTRODE CONDUCTOR INDICATED ON THE |
| PLANS IS UNDERSIZED. PRODIDE ADAQUATE GEC SIZE PER NEC |
| 250.66. |
| |
| 2) PROVIDE A SITE PLAN TO INDICATE THE LOCATION OF THE |
| ELECTRICAL PANEL TO BE CHANGED TO ILLUSTRATE THE |
| REQUIRED SERVICE ENTRANCE OVER CURRENT PROTECTIVE |
| DEVICE AS PER NEC 230.91 LOCATION. |
| REVISE THE RISER DIAGRAM TO INDICATE THE LOCATION OF |
| THE MAIN DISCONNECT (SERVICE OCPD) |
| |
| 3) REVISE THE VALUATION OF THE PROJECT INDICATED ON THE |
| PERMIT APPLICATION AND PROVIDE SUPPORTING DOCUMENTATION |
| FOR THE VALUATION OF THE PROJECT ON THE APPLICATION. |
| INCLUDE ALL LABOR MATERIAL, SUB CONTRACTS ASSOCIATED |
| UTLITY COSTS OVERHEAD PROFIT ETC... FBC WPB AMENDMENTS. |
| SECTION 109.3 |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT |
| /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM |
| ITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| SHEETS FOR COMPARATIVE REVIEW. |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |