Plan Review Notes
Plan Review Notes For Permit 14080649
Permit Number 14080649
Review Stop E
Sequence Number 2
Notes
Date Text
2014-09-21 13:48:53TO S.H'S DESK
  
  
  
2014-09-21 13:48:00DATE: 9/21/2014
 PROJECT: SOUTHWIND PLAZA
 PERMIT#: 14080649
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 2ND ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 1) INSTALLATION SHALL COMPLY WITH THE PROVISIONS OF THE
 NEC ARTICLE 410 PART XIII AND THE FBC - ENERGY CHAPTER
 5 SECTION 505.2.4 EXTERIOR LIGHTING CONTROLS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  