Plan Review Notes For Permit 14080649 |
Permit Number |
14080649 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2014-09-21 13:48:53 | TO S.H'S DESK | | | | | | | 2014-09-21 13:48:00 | DATE: 9/21/2014 | | PROJECT: SOUTHWIND PLAZA | | PERMIT#: 14080649 | | CODE: 2008 EDITION OF THE NEC | | 2010 EDITION OF THE FBC | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | 2ND ELECTRICAL PLAN REVIEW | | ACTION: PROVISO | | | | 1) INSTALLATION SHALL COMPLY WITH THE PROVISIONS OF THE | | NEC ARTICLE 410 PART XIII AND THE FBC - ENERGY CHAPTER | | 5 SECTION 505.2.4 EXTERIOR LIGHTING CONTROLS. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. SEE LINK: | | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ | | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO | | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED | | SHEETS FOR COMPARATIVE REVIEW. | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] | | |
|