Plan Review Notes For Permit 14080626 |
Permit Number |
14080626 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2014-08-27 09:11:15 | DATE: 8/27/2014 | | PROJECT: NALBANDIAN 400 N. FLAGLER | | PERMIT#: 14080626 | | CODE: 2008 EDITION OF THE NEC | | 2010 EDITION OF THE FBC | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | 2ND ELECTRICAL PLAN REVIEW | | ACTION: APPROVED WITH EXCEPTION | | | | 1) METAL FRAMING MEMBERS SHALL BE BONDED TO THE | | EQUIPMENT GROUNDING CONDUCTOR FOR THE CIRCUIT THAT MAY | | ENERGIZE THE FRAMING AND BE SIZED IN ACCORDANCE WITH | | THE NEC TABLE 250.122. FOR THE PURPOSE OF THIS SECTION, | | A GROUNDED METAL OUTLET BOX ATTACHED TO THE FRAMING | | SHALL BE PERMITTED. AS REQUIRED. | | | | 2) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER | | RESISTANT AND AFCI PROTECTED. NEC 210.12, NEC 406.11. | | INDICATE NOTE TO INCLUDE TAMPER RESISTANT RECEPTACLES | | AND SUBMIT WITH ASBUITS. | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] | | |
|