2014-08-15 08:03:41DATE: 8/15/2014
 PROJECT: NALBANDIAN 400 N. FLAGLER
 PERMIT#: 14080626
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) WHEN ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL
 314.3 AND 314.3.1. INDICATE LOCATION OF NEW AND/OR
 EXISTING SMOKE DETECTORS AND SUBMIT WITH ASBUILTS.
  
 2) LUMINAIRES IN CLOTHES CLOSETS SHALL BE INSTALLED IN
 ACCORDANCE WITH THE PROVISIONS OF THE NEC 410.16(A) AND
 (B). INDICATE THE LOCATION OF THE FIXTURES IN THE
 CLOTHES CLOSETS AND SUBMIT WITH ASBUILTS
  
 3) METAL FRAMING MEMBERS SHALL BE BONDED TO THE
 EQUIPMENT GROUNDING CONDUCTOR FOR THE CIRCUIT THAT MAY
 ENERGIZE THE FRAMING AND BE SIZED IN ACCORDANCE WITH
 THE NEC TABLE 250.122. FOR THE PURPOSE OF THIS SECTION,
 A GROUNDED METAL OUTLET BOX ATTACHED TO THE FRAMING
 SHALL BE PERMITTED. AS REQUIRED.
  
 4) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER
 RESISTANT AND AFCI PROTECTED. NEC 210.12, NEC 406.11.
 INDICATE NOTE TO INCLUDE TAMPER RESISTANT RECEPTACLES
 AND SUBMIT WITH ASBUITS.
  
 5) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. WPB AMENDMENTS
 TO FBC 107.2.1. SIGN PLANS AND SUBMIT WITH ASBUILTS.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,