2014-08-15 08:03:41 | DATE: 8/15/2014 |
| PROJECT: NALBANDIAN 400 N. FLAGLER |
| PERMIT#: 14080626 |
| CODE: 2008 EDITION OF THE NEC |
| 2010 EDITION OF THE FBC |
| 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| |
| 1ST ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| 1) WHEN ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A |
| PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE |
| ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS |
| LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL |
| 314.3 AND 314.3.1. INDICATE LOCATION OF NEW AND/OR |
| EXISTING SMOKE DETECTORS AND SUBMIT WITH ASBUILTS. |
| |
| 2) LUMINAIRES IN CLOTHES CLOSETS SHALL BE INSTALLED IN |
| ACCORDANCE WITH THE PROVISIONS OF THE NEC 410.16(A) AND |
| (B). INDICATE THE LOCATION OF THE FIXTURES IN THE |
| CLOTHES CLOSETS AND SUBMIT WITH ASBUILTS |
| |
| 3) METAL FRAMING MEMBERS SHALL BE BONDED TO THE |
| EQUIPMENT GROUNDING CONDUCTOR FOR THE CIRCUIT THAT MAY |
| ENERGIZE THE FRAMING AND BE SIZED IN ACCORDANCE WITH |
| THE NEC TABLE 250.122. FOR THE PURPOSE OF THIS SECTION, |
| A GROUNDED METAL OUTLET BOX ATTACHED TO THE FRAMING |
| SHALL BE PERMITTED. AS REQUIRED. |
| |
| 4) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER |
| RESISTANT AND AFCI PROTECTED. NEC 210.12, NEC 406.11. |
| INDICATE NOTE TO INCLUDE TAMPER RESISTANT RECEPTACLES |
| AND SUBMIT WITH ASBUITS. |
| |
| 5) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| THE PERSON RESPONSIBLE FOR THE DESIGN. WPB AMENDMENTS |
| TO FBC 107.2.1. SIGN PLANS AND SUBMIT WITH ASBUILTS. |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |