Plan Review Notes
Plan Review Notes For Permit 14080586
Permit Number 14080586
Review Stop E
Sequence Number 3
Notes
Date Text
2014-11-03 12:55:22TO JG'S DESK.
  
  
2014-11-03 12:14:23DATE: 11/3/2014
 PROJECT: BARCELONA RD RENNOVATION
 PERMIT#: 14080856
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 3RD ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 1) INDICATE THE LOCATION FOR THE ELECTRICAL PANELS.
 2010 WPB AMENDMENTS TO THE FBC107.3.5
  
 2) REVISE PANEL SCHEDULE "A" TO CORRECT PROBABLE TYPO
 FOR "KITCHEN" CIRCUIT #23 INDICATING A SINGLE POLE
 60AMP OCPD WITH #6 WIRE.
 WHICH 110V 1POLE CIRCUIT IS IDENTIFIED AS "KITCHEN"?
 PLEASE CLARIFY BY INDICATING CIRCUIT NUMBERS ON THE
 FLOOR PLAN TO CORRESPOND TO CIRCUIT NUMBERS ON THE
 PANEL SCHEDULES.
  
 3) REVISE THE RISER DIAGRAM AN VERIFY THE METAL NATURAL
 GAS PIPING BE BONDED IN ACCORDANCE WITH THE NEC
 250.104(B)
  
 4) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS
 HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT
 NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE
 INTERRUPTED. NEC 110.9
  
 5) VERIFY LUMINAIRES AND EXHAUST FANS LOCATED IN THE
 BATHROOMS OVER BATHTUB OR SHOWER SHALL BE IN ACCORDANCE
 WITH THE NEC 410.10(D) BATHTUB AND SHOWER, AND
 NEC110.3(B) LISTING AND LABELING
  
 6) VERIFY ALL RECEPTACLE OUTLETS INSTALLED THROUGHOUT
 THE HOUSE SHALL BE INSTALLED IN COMPLIANCE WITH NEC
 210.52(A)(1) SHALL BE INSTALLED SUCH THAT NO POINT
 MEASURED HORIZONTALLY ALONG THE FLOOR LINE IN ANY WALL
 SPACE IS MORE THAN (6 FT) FROM A RECEPTACLE OUTLET.
  
 7) A GFI OUTLET SHALL BE INSTALLED AT EACH COUNTERTOP
 SPACE THAT IS 12" OR WIDER. GFI OUTLETS SHALL BE
 INSTALLED SO THAT NO POINT ALONG THE WALL LINE IS MORE
 THAN 24" HORIZONTALLY FROM AN OUTLET IN THAT SPACE. NEC
 210.52(C)(1). THERE APPEAR TO BE ADDITIONAL OUTLETS
 REQUIRED AT COUNTERTOP WALL SPACE AREAS IN THE KITCHEN.
  
 8) ALL 125V SINGLE PHASE, 15 AND 20AMP RECEPTACLES
 INSTALLED IN THE LOCATIONS SPECIFIED IN (1) THROUGH (8)
 SHALL HAVE GROUND FAULT CIRCUIT INTERRUPTER PROTECTION
 FOR PERSONNEL. ALL OUTLETS IN THE KITCHEN, BATHROOM,
 OUTDOORS, LAUNDRY, UTILITY, AND WET BAR SINKS SHALL BE
 GFCI PROTECTED. NEC 210.8.
  
 9) METAL FRAMING MEMBERS SHALL BE BONDED TO THE
 EQUIPMENT GROUNDING CONDUCTOR FOR THE CIRCUIT THAT MAY
 ENERGIZE THE FRAMING AND BE SIZED IN ACCORDANCE WITH
 THE NEC TABLE 250.122. FOR THE PURPOSE OF THIS SECTION,
 A GROUNDED METAL OUTLET BOX ATTACHED TO THE FRAMING
 SHALL BE PERMITTED. FBC 2704
  
 SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR SECURITY, CCTV, STUCTURED CABLING,
 NETWORK, AUDIO/VIDEO, GENERATOR, SWIMMING POOL,
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]