2014-11-03 12:55:22 | TO JG'S DESK. |
| |
| |
2014-11-03 12:14:23 | DATE: 11/3/2014 |
| PROJECT: BARCELONA RD RENNOVATION |
| PERMIT#: 14080856 |
| CODE: 2008 EDITION OF THE NEC |
| 2010 EDITION OF THE FBC |
| 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| |
| 3RD ELECTRICAL PLAN REVIEW |
| ACTION: PROVISO |
| |
| 1) INDICATE THE LOCATION FOR THE ELECTRICAL PANELS. |
| 2010 WPB AMENDMENTS TO THE FBC107.3.5 |
| |
| 2) REVISE PANEL SCHEDULE "A" TO CORRECT PROBABLE TYPO |
| FOR "KITCHEN" CIRCUIT #23 INDICATING A SINGLE POLE |
| 60AMP OCPD WITH #6 WIRE. |
| WHICH 110V 1POLE CIRCUIT IS IDENTIFIED AS "KITCHEN"? |
| PLEASE CLARIFY BY INDICATING CIRCUIT NUMBERS ON THE |
| FLOOR PLAN TO CORRESPOND TO CIRCUIT NUMBERS ON THE |
| PANEL SCHEDULES. |
| |
| 3) REVISE THE RISER DIAGRAM AN VERIFY THE METAL NATURAL |
| GAS PIPING BE BONDED IN ACCORDANCE WITH THE NEC |
| 250.104(B) |
| |
| 4) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS |
| HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT |
| NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE |
| INTERRUPTED. NEC 110.9 |
| |
| 5) VERIFY LUMINAIRES AND EXHAUST FANS LOCATED IN THE |
| BATHROOMS OVER BATHTUB OR SHOWER SHALL BE IN ACCORDANCE |
| WITH THE NEC 410.10(D) BATHTUB AND SHOWER, AND |
| NEC110.3(B) LISTING AND LABELING |
| |
| 6) VERIFY ALL RECEPTACLE OUTLETS INSTALLED THROUGHOUT |
| THE HOUSE SHALL BE INSTALLED IN COMPLIANCE WITH NEC |
| 210.52(A)(1) SHALL BE INSTALLED SUCH THAT NO POINT |
| MEASURED HORIZONTALLY ALONG THE FLOOR LINE IN ANY WALL |
| SPACE IS MORE THAN (6 FT) FROM A RECEPTACLE OUTLET. |
| |
| 7) A GFI OUTLET SHALL BE INSTALLED AT EACH COUNTERTOP |
| SPACE THAT IS 12" OR WIDER. GFI OUTLETS SHALL BE |
| INSTALLED SO THAT NO POINT ALONG THE WALL LINE IS MORE |
| THAN 24" HORIZONTALLY FROM AN OUTLET IN THAT SPACE. NEC |
| 210.52(C)(1). THERE APPEAR TO BE ADDITIONAL OUTLETS |
| REQUIRED AT COUNTERTOP WALL SPACE AREAS IN THE KITCHEN. |
| |
| 8) ALL 125V SINGLE PHASE, 15 AND 20AMP RECEPTACLES |
| INSTALLED IN THE LOCATIONS SPECIFIED IN (1) THROUGH (8) |
| SHALL HAVE GROUND FAULT CIRCUIT INTERRUPTER PROTECTION |
| FOR PERSONNEL. ALL OUTLETS IN THE KITCHEN, BATHROOM, |
| OUTDOORS, LAUNDRY, UTILITY, AND WET BAR SINKS SHALL BE |
| GFCI PROTECTED. NEC 210.8. |
| |
| 9) METAL FRAMING MEMBERS SHALL BE BONDED TO THE |
| EQUIPMENT GROUNDING CONDUCTOR FOR THE CIRCUIT THAT MAY |
| ENERGIZE THE FRAMING AND BE SIZED IN ACCORDANCE WITH |
| THE NEC TABLE 250.122. FOR THE PURPOSE OF THIS SECTION, |
| A GROUNDED METAL OUTLET BOX ATTACHED TO THE FRAMING |
| SHALL BE PERMITTED. FBC 2704 |
| |
| SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY |
| MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS |
| ARE REQUIRED FOR SECURITY, CCTV, STUCTURED CABLING, |
| NETWORK, AUDIO/VIDEO, GENERATOR, SWIMMING POOL, |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| SHEETS FOR COMPARATIVE REVIEW. |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |