2014-10-09 10:21:39 | DATE: 10/21/2014 |
| PROJECT: BARCELONA RD RENNOVATION |
| PERMIT#: 14080856 |
| CODE: 2008 EDITION OF THE NEC |
| 2010 EDITION OF THE FBC |
| 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| |
| 2ND ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| 1) REVISE THE RISER DIAGRAM TO INDICATE A LOGICAL |
| DESIGN UTILIZING FULL SIZE SERVICE ENTRANCE CONDUCTORS |
| FEEDING PANELS "A" AND "B" NEC 310.15.(B)(6) . |
| |
| 2) REVISE THE RISER DIAGRAM TO INCLUDE AN EQUIPMENT |
| GROUNDING CONDUCTOR IN THE FEEDER TO THE GARAGE PANEL. |
| NEC 250.122 |
| |
| 3) REVISE THE PANEL "A" SCHEDULE TO TO CORRECT PROBABLE |
| TYPO FOR KITCHEN CIRCUIT #23 INDICATING A 60AMP OCPD |
| WITH #12 WIRE. |
| |
| 4) CLARIFY THE TYPE, RATING, SIZE AND USE FOR THE |
| GUTTER INDICATED ABOVE PANELS "A" AND "B" ON THE RISER |
| DIAGRAM. WPB AMENDMENTS TO THE FBC 107.3.2 |
| |
| 5) VERIFY LUMINAIRES IN CLOTHES CLOSETS SHALL BE |
| INSTALLED IN ACCORDANCE WITH THE PROVISIONS OF THE NEC |
| 410.16(A) AND (B). |
| |
| 6) VERIFY ALL RECEPACLE OUTLETS INSTALLED THROUGHOUT |
| SHALL BE IN COMPLIANCE WITH NEC 210.52(A)(1) SHALL BE |
| INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY |
| ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 1.8 |
| M (6 FT) FROM A RECEPTACLE OUTLET. |
| |
| 7) INDICATE THE REQUIRED WORKING CLEARANCES FOR THE A/C |
| DISCONNECTS. SEE NEC 110.26 |
| SUFFICIENT ACCESS AND WORKING SPACE SHALL BE PROVIDED |
| AND MAINTAINED ABOUT ALL ELECTRICAL EQUIPMENT TO PERMIT |
| READY AND SAFE OPERATION AND MAINTENANCE OF SUCH |
| EQUIPMENT. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| SHEETS FOR COMPARATIVE REVIEW. |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |