2014-09-17 17:04:07DATE: 9/17/2014
 PROJECT: BARCELONA RD RENNOVATION
 PERMIT#: 14080856
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) ADDITIONAL RECEPTACLES ARE REQUIRED. ADD RECEPTACLES
 SO THAT NO WALL SPACE IS MORE THAN 6 FEET FROM A
 RECEPTACLE AND ALL WALL SPACES MORE THAN 2 FEET IN
 WIDTH HAVE A RECEPTACLE. NEC 210.52(A)(1)
  
 2) AT LEAST ONE RECEPTACLE SHALL BE INSTALLED AT EACH
 ISLAND COUNTERTOP SPACE WITH ALONG DIMENSION OF 600 MM
 (24 IN.) OR GREATER AND A SHORT DIMENSION OF 300 MM (12
 IN.) OR GREATER.NEC 210.52(C)(2)
  
 3) KITCHEN COUNTER TOP RECEPTACLES SHALL BE SUPPLIED BY
 NO FEWER THAN TWO SMALL APPLIANCE BRANCH CIRCUITS. NEC
 210.52 (B)(3)
  
 4) ALL NEW GENERAL PURPOSE OUTLETS MUST BE AFCI
 PROTECTED. NEC 210.12 NEW RECEPTACLES MUST BE TAMPER
 RESISTANT. NEC 406.11
  
 5) FOR A ONE FAMILY DWELLING AND EACH UNIT OF A
 TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST
 ONE RECEPTACLE OUTLET ACCESSIBLE WHILE STANDING AT
 GRADE LEVEL AND LOCATED NOT MORE THAN 2.0 M (61.2 FT)
 ABOVE GRADE SHALL BE INSTALLED AT THE FRONT AND BACK OF
 THE DWELLING. NEC 210.52(E)(3)
  
 6) PROVIDE A LIGHTING OUTLET AND SWITCH FOR ATTIC
 ACCESS. 210.70(A)(3)
  
 7) INDICATE THE LOCATION FOR THE ELECTRICAL PANELS.
  
 8) INDICATE LOCATION OF A/C CONDENSING UNITS AND THE
 ELECTRICAL CIRCUITS AND REQUIRED DISCONNECTS.
  
 9) ONE 125VOLT, SINGLE-PHASE, 15 OR 20AMP GFI
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HEATING,
 AIR-CONDITIONING, AND REFRIGERATION EQUIPMENT. THE
 RECEPTACLE SHALL BE LOCATED ON THE SAME LEVEL AND
 WITHIN 25FT OF THE HEATING, AIR-CONDITIONING, AND
 REFRIGERATION EQUIPMENT. THE RECEPTACLE OUTLET SHALL
 NOT BE CONNECTED TO THE LOAD SIDE OF THE EQUIPMENT
 DISCONNECTING MEANS. NEC 210.63 SEE 210.8(A)(3),
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  