2014-09-17 17:04:07 | DATE: 9/17/2014 |
| PROJECT: BARCELONA RD RENNOVATION |
| PERMIT#: 14080856 |
| CODE: 2008 EDITION OF THE NEC |
| 2010 EDITION OF THE FBC |
| 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| |
| 1ST ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| 1) ADDITIONAL RECEPTACLES ARE REQUIRED. ADD RECEPTACLES |
| SO THAT NO WALL SPACE IS MORE THAN 6 FEET FROM A |
| RECEPTACLE AND ALL WALL SPACES MORE THAN 2 FEET IN |
| WIDTH HAVE A RECEPTACLE. NEC 210.52(A)(1) |
| |
| 2) AT LEAST ONE RECEPTACLE SHALL BE INSTALLED AT EACH |
| ISLAND COUNTERTOP SPACE WITH ALONG DIMENSION OF 600 MM |
| (24 IN.) OR GREATER AND A SHORT DIMENSION OF 300 MM (12 |
| IN.) OR GREATER.NEC 210.52(C)(2) |
| |
| 3) KITCHEN COUNTER TOP RECEPTACLES SHALL BE SUPPLIED BY |
| NO FEWER THAN TWO SMALL APPLIANCE BRANCH CIRCUITS. NEC |
| 210.52 (B)(3) |
| |
| 4) ALL NEW GENERAL PURPOSE OUTLETS MUST BE AFCI |
| PROTECTED. NEC 210.12 NEW RECEPTACLES MUST BE TAMPER |
| RESISTANT. NEC 406.11 |
| |
| 5) FOR A ONE FAMILY DWELLING AND EACH UNIT OF A |
| TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST |
| ONE RECEPTACLE OUTLET ACCESSIBLE WHILE STANDING AT |
| GRADE LEVEL AND LOCATED NOT MORE THAN 2.0 M (61.2 FT) |
| ABOVE GRADE SHALL BE INSTALLED AT THE FRONT AND BACK OF |
| THE DWELLING. NEC 210.52(E)(3) |
| |
| 6) PROVIDE A LIGHTING OUTLET AND SWITCH FOR ATTIC |
| ACCESS. 210.70(A)(3) |
| |
| 7) INDICATE THE LOCATION FOR THE ELECTRICAL PANELS. |
| |
| 8) INDICATE LOCATION OF A/C CONDENSING UNITS AND THE |
| ELECTRICAL CIRCUITS AND REQUIRED DISCONNECTS. |
| |
| 9) ONE 125VOLT, SINGLE-PHASE, 15 OR 20AMP GFI |
| RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE |
| LOCATION FOR THE SERVICING OF HEATING, |
| AIR-CONDITIONING, AND REFRIGERATION EQUIPMENT. THE |
| RECEPTACLE SHALL BE LOCATED ON THE SAME LEVEL AND |
| WITHIN 25FT OF THE HEATING, AIR-CONDITIONING, AND |
| REFRIGERATION EQUIPMENT. THE RECEPTACLE OUTLET SHALL |
| NOT BE CONNECTED TO THE LOAD SIDE OF THE EQUIPMENT |
| DISCONNECTING MEANS. NEC 210.63 SEE 210.8(A)(3), |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| SHEETS FOR COMPARATIVE REVIEW. |
| |