Plan Review Notes
Plan Review Notes For Permit 14080586
Permit Number 14080586
Review Stop B
Sequence Number 1
Notes
Date Text
2014-09-11 19:00:07RESIDENTIAL (R3) ADDITION/ALTERATION, BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- BOTH SET OF PLANS SUBMITTED NEED TO BE SIGNED AND
 SEALED BY THE ARCHITECT OF RECORD AS REQUIRED BY
 CHAPTER 481 FLORIDA STATUTES.
 ***NOTE: MAKE SURE BOTH SETS ARE THE SAME. ONE SET
 SUBMITTED WAS DATED 05/15/2014 AND THE OTHER ONE WAS
 DATED 07/01/2014. COORDINATE THE DRAWINGS BEFORE
 RE-SUBMITTAL TO AVOID CONFLICTS AND DELAYS.
  
 2- BRING PLANS TO PALM BEACH COUNTY TO VERIFY IF IMPACT
 FEES ARE DUE. BRING BACK COUNTY STAMPED PLANS AND COPY
 OF PAID RECEIPT IF FEES ARE DUE. REQUIRED BY THE COUNTY
 IMPACT FEE ORDINANCE OF THE LAND DEVELOPMENT CODE.
  
 3- SHEET SP-1:
 A) NOTE REGARDING THE EXISTING BUILDING ALTERATION
 LEVEL IS INCOMPLETE. COMPLETE THE ALTERATION LEVEL
 INFORMATION AND ALSO KEEP IN MIND THAT THIS IS AN
 ADDITION ALSO. SEC. 401.4 OF 2010 FBC-EXISTING BUILDING
  
 B) FIRE DEPARTMENT NOTES AND REFERENCED CODE SECTIONS
 DON'T APPLY TO SINGLE FAMILY RESIDENCES. THESE NOTES
 ARE NOT NEED IT. REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS TO FBC.
  
 4- NEW MASTER BEDROOM EGRESS WINDOWS: PROVIDE
 MANUFACTURERS CUT SHEETS SHOWING SIZES SPECIFIED IN
 PLANS TO VERIFY COMPLIANCE WITH THE EGRESS REQUIREMENTS
 OF SEC. R310 OF 2010 FBC-RESIDENTIAL.
  
 5- PROVIDE ICYNENE EVALUATION REPORT TO SHOW COMPLIANCE
 WITH SEC. R316.
  
 6- SHEET S4:
 A) PROVIDE COMPLETE SPECIFICATIONS FOR THE TYPE OF
 SECOND FLOOR SHEATHING AND ROOF SHEATHING. THERE IS NO
 INFORMATION ON PLANS. SEC. R301 OF 2010
 FBC-RESIDENTIAL.
  
 B) ROOF SHEATHING NAILS NEED TO BE RING SHANK NAILS AS
 REQUIRED BY SEC. R803.2.3.1 OF 2010 FBC-RESIDENTIAL.
 CLEARLY INDICATE THAT NAILS NEED TO BE RING SHANK
 NAILS.
  
 7- A) DESIGN PROFESSIONAL TO CLEARLY SPECIFY ON PLANS
 TYPE OF ROOFING SYSTEM, MATERIALS AND FASTENING AS
 REQUIRED BY SEC. 107.2.1.2 OF CITY AMENDMENTS TO FBC.
 (NOTE: IF USING FOAM ADHESIVE FOR TILE INSTALLATION,
 THEN, CLEARLY IDENTIFY ON TABLE 3A-2 OF FLORIDA PRODUCT
 APPROVAL FL7804-R7 SUBMITTED WHICH ADHESIVE IS GOING TO
 BE USED TO VERIFY COMPLIANCE WITH THE ATTACHMENT
 RESISTANCE).
  
 B) PRODUCT APPROVAL FL14317-R5 ROOFING UNDERLAYMENT
 SUBMITTED MAY NOT BE USED. DESIGN PRESSURES SHOWN ON
 LIMITATION 5.5.2 THRU 5.5.2.3 DON'T MEET THE REQUIRED
 DESIGN PRESSURES OF SEC. R301. NEED TO USE ANOTHER
 PRODUCT. AND, COORDINATE WITH ITEMS #6(C) AND #7(A)
 ABOVE.
  
 C) PRODUCT APPROVAL FL11915-R3 SUBMITTED. CLEARLY
 SPECIFY WHICH SPECIFIC UNDERLAYMENT IS GOING TO BE
 USED. COORDINATE WITH DESIGN PROFESSIONAL
 SPECIFICATIONS REQUIRED BY ITEM # 7(A) ABOVE.
  
 8- PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS
 FOR THE INSTALLATION OF THE ROUND WINDOW AS SPECIFIED
 ON PLANS. SEC. R612.10.2 OF 2010 FBC-RESIDENTIAL.
  
 9- PROVIDE PROVIDE PRODUCT APPROVAL (2 COPIES) AS
 REQUIRED BY DCA RULE 9N-3 FOR:
 A) ROOF TILE UNDERLAYMENT IF USING SELF ADHERING
 UNDERLAYMENT. FLORIDA PRODUCT APPROVAL FL14317-R5
 SUBMITTED CAN'T BE USED. SEE ITEM #7(B) ABOVE.
  
 B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON ALL
 DETAILS/ SECTIONS AND SPECIFICATIONS. (NOTE: PROVIDE
 ONLY THE PRODUCT APPROVAL COVER PAGE AND PAGE SHOWING
 THE CONNECTOR OR WRITE DOWN THE PRODUCT APPROVAL NUMBER
 NEXT TO THE SPECIFIED STRUCTURAL CONNECTORS IN ALL
 DETAILS).
  
 10- DESIGN PROFESSIONAL OF RECORD TO REVIEW AND APPROVE
 IN WRITING (NOT SIGNING AND SEALING) ALL PRODUCT
 APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS
 TO FBC.
  
 ***NOTES:
 *** PROVIDE RESPONSE LETTER ADDRESSING EACH COMMENT TO
 EXPEDITE THE REVIEW PROCESS.
 *** PLEASE REMOVE AND REPLACE ANY REVISED SHEET WHEN
 RE-SUBMITTING TO EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]