Plan Review Notes For Permit 14080344 |
Permit Number |
14080344 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-08-20 12:13:19 | 1ST REVIEW 2010 FBC- | | 1) SUBMITTED GAS TABLE IS FROM THE 2004 FBC. SUBMIT | | APPLICABLE GAS TABLE FROM THE 2010 FBC GAS CODE. | | 2) SUBMIT ADDITIONAL SPECS FOR THE GENERATOR. GENERATOR | | SHALL COMPLY W/ UL 2200 & NFPA 37. | | 3) GENERATOR SHALL BE 5 FT. FROM THE BUILDING WALL PER | | NFPA 37. | | 4)SHOW THE LOCATION OF ALL BUILDING OPENINGS IN | | RELATION TO THE GENERATOR EXHAUST. EXHAUST SHALL BE | | MIN. 10 FT. FROM BUILDING OPENINGS. | | | | T. LARGE | | 561-805-6692 |
|