Date |
Text |
2014-09-25 09:47:12 | DATE: 9/25/2014 |
| PROJECT: KITCHEN AND BATH REMODEL |
| PERMIT#: 14080339 |
| CODE: 2008 EDITION OF THE NEC |
| 2010 EDITION OF THE FBC |
| 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| |
| 1ST ELECTRICAL PLAN REVIEW |
| ACTION: PROVISO |
| |
| 1) LIGHTING OUTLETS SHALL BE INSTALLED WHERE SPECIFIED |
| IN NEC 210.70(A)1,2,3 |
| (1) HABITABLE ROOMS. AT LEAST ONE WALL |
| SWITCH?CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED IN |
| EVERY HABITABLE ROOM AND BATHROOM. |
| (2) ADDITIONAL LOCATIONS. ADDITIONAL LIGHTING OUTLETS |
| SHALL BE INSTALLED IN ACCORDANCE WITH (A)(2)(A), |
| (A)(2)(B), AND (A)(2)(C). |
| (3) STORAGE OR EQUIPMENT SPACES. FOR ATTICS, UNDERFLOOR |
| SPACES, UTILITY ROOMS, AND BASEMENTS, AT LEAST ONE |
| LIGHTING OUTLET CONTAINING A SWITCH OR CONTROLLED BY A |
| WALL SWITCH SHALL BE INSTALLED WHERE THESE SPACES ARE |
| USED FOR STORAGE OR CONTAIN EQUIPMENT REQUIRING |
| SERVICING. |
| |
| 2) FOR A ONE FAMILY DWELLING AND EACH UNIT OF A |
| TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST |
| ONE RECEPTACLE OUTLET ACCESSIBLE WHILE STANDING AT |
| GRADE LEVEL AND LOCATED NOT MORE THAN 2.0 M (61.2 FT) |
| ABOVE GRADE SHALL BE INSTALLED AT THE FRONT AND BACK OF |
| THE DWELLING. NEC 210.52(E)(3) |
| |
| 3) METAL FRAMING MEMBERS SHALL BE BONDED TO THE |
| EQUIPMENT GROUNDING CONDUCTOR FOR THE CIRCUIT THAT MAY |
| ENERGIZE THE FRAMING AND BE SIZED IN ACCORDANCE WITH |
| THE NEC TABLE 250.122. FOR THE PURPOSE OF THIS SECTION, |
| A GROUNDED METAL OUTLET BOX ATTACHED TO THE FRAMING |
| SHALL BE PERMITTED. |
| |
| 4) ALL 125V SINGLE PHASE, 15 AND 20AMP RECEPTACLES |
| INSTALLED IN THE LOCATIONS SPECIFIED IN (1) THROUGH (8) |
| SHALL HAVE GROUND FAULT CIRCUIT INTERRUPTER PROTECTION |
| FOR PERSONNEL. ALL OUTLETS IN THE GARAGE SHALL BE GFCI |
| PROTECTED. NEC 210.8. |
| |
| 5) FOR A ONE FAMILY DWELLING AND EACH UNIT OF A |
| TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST |
| ONE RECEPTACLE OUTLET ACCESSIBLE WHILE STANDING AT |
| GRADE LEVEL AND LOCATED NOT MORE THAN 2.0 M (61.2 FT) |
| ABOVE GRADE SHALL BE INSTALLED AT THE FRONT AND BACK OF |
| THE DWELLING. NEC 210.52(E)(3) |
| |
| 6) OCCUPIABLE BALCONIES AND PORCHES OVER 20 SQ FT MUST |
| NOW HAVE A RECEPTACLE OUTLET (GFCI PROTECTED) |
| (210.52(E)(3). |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| SHEETS FOR COMPARATIVE REVIEW. |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |