Plan Review Notes
Plan Review Notes For Permit 14080339
Permit Number 14080339
Review Stop E
Sequence Number 1
Notes
Date Text
2014-09-16 11:02:38DATE: 9/16/2014
 PROJECT: BATHROOM AND KITCHEN RENNOVATION
 PERMIT#: 14080339
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) FLOOR PLAN TO BE REVISED TO SHOW ALL REQUIRED
 RECEPTACLE OUTLETS IN THE KITCHEN AND BATH. BATHROOM
 BRANCH CIRCUITS IN ADDITION TO THE NUMBER OF BRANCH
 CIRCUITS REQUIRED BY OTHER PARTS OF THIS SECTION, AT
 LEAST ONE 20-AMPERE BRANCH CIRCUIT SHALL BE PROVIDED TO
 SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH CIRCUITS
 SHALL HAVE NO OTHER OUTLETS. PLEASE INDICATE COMPLIANCE
 WITH THE NEC ARTICLE 210.11(C)(3)
  
 2) KITCHEN COUNTER TOP RECEPTACLES SHALL BE SUPPLIED BY
 NO FEWER THAN TWO SMALL APPLIANCE BRANCH CIRCUITS. NEC
 210.52(B)(3) AT LEAST ONE RECEPTACLE OUTLET SHALL BE
 INSTALLED AT EACH ISLAND COUNTERTOP SPACE WITH A LONG
 DIMENSION OF 24" OR GREATER AND A SHORT DIMENSION OF
 12" OR GREATER. NEC 210.52(C)(2)
  
 3) INDICATE OR VERIFY THE INSTALLATION OF SMOKE AND CO
 DETECTORS AT ALL SLEEPING ROOMS. WHEN ALTERATIONS,
 REPAIRS, OR ADDITIONS REQUIRING A PERMIT OCCUR, OR WHEN
 ONE OR MORE SLEEPING ROOMS ARE ADDED OR CREATED IN
 EXISTING DWELLINGS, THE INDIVIDUAL DWELLING UNIT SHALL
 BE EQUIPPED WITH SMOKE ALARMS LOCATED AS REQUIRED FOR
 NEW DWELLINGS. FBC-RESIDENTIAL 314 AND 315. REVISE PLAN
 TO INDICATE OR VERIFY THE REQUIRED SMOKE AND CO
 DETECTORS.
  
 4) ALL NEW GENERAL PURPOSE OUTLETS MUST BE AFCI
 PROTECTED. NEC 210.12 REVISE ACCORDINGLY
  
 5) NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
 REVISE ACCORDINGLY
  
 6) OUTLET BOXES OR OUTLET BOX SYSTEMS USED AS THE SOLE
 SUPPORT OF A CEILING-SUSPENDED (PADDLE) FAN SHALL BE
 LISTED, SHALL BE MARKED BY THEIR MANUFACTURER AS
 SUITABLE FOR THIS PURPOSE, AND SHALL NOT SUPPORT
 CEILING-SUSPENDED (PADDLE) FANS THAT WEIGH MORE THAN 32
 KG (70 LB). FOR OUTLET BOXES OR OUTLET BOX SYSTEMS
 DESIGNED TO SUPPORT CEILING-SUSPENDED (PADDLE) FANS
 THAT WEIGH MORE THAN 16 KG (35 LB), THE REQUIRED
 MARKING SHALL INCLUDE THE MAXIMUM WEIGHT TO BE
 SUPPORTED. NEC314.27(D) REVISE ACCORDINGLY
  
 7) CLAIRFICATION IS REQUIRED. THERE ARE NUMBER AND
 LLETTER DESIGNATIONS USED THROUGHOUT THE PLAN HOWEVER
 THERE IS NO SYMBOLS KEY USED FOR REFFERENCE. REVISE
 PLAN FOR CLAIRIFICATION. WPB AMENDMENTS TO THE FBC
 107.3.2
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  