Plan Review Notes For Permit 14080325 |
Permit Number |
14080325 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2014-10-08 15:35:38 | 504.5 MAKEUP AIR. | | INSTALLATIONS EXHAUSTING MORE THAN 200 CFM (0.09M3/S) | | SHALL BE PROVIDED WITH MAKEUP AIR | | | | PLEASE PROVIDE A DUCT OR DOOR GRILL INTO THE LAUNDRY | | AREA FROM THE CORRIDOR TO PROVIDE REQUIRED M/U AIR | | AND SHOW DRYER DUCT TO THE OUTSIDE | | | | |
|