2014-08-12 14:38:15THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THIS OCCUPANCY AND PROPOSED PLAN SHALL MEET OR EXCEED
 THE REQUIREMENTS OF NFPA 150, FIRE AND LIFE SAFETY IN
 ANIMAL HOUSING FACILITIES.
  
 THE BUILDING PLAN DOES NOT INCLUDE THE BUILDING SQUARE
 FOOTAGE AND CONSTRUCTION TYPE/CLASS, ROOF SYSTEM.
  
 A LIFE SAFETY PLAN, INCLUDING ALL OCCUPANCY COUNTS,
 HUMAN AND ANIMAL, COMMON PATHS OF TRAVEL, EXITS, EXIT
 DISCHARGES AND FIRE EXTINGUISHER LOCATIONS SHALL BE
 INCLUDED.
  
 AN EXIT PATH SHALL NOT EXCEED 75 FEET FROM ANY AREA OF
 THE BUUILDING.
  
 A NFPA 72 COMPLIANT FIRE ALARM SYSTEM IS REQUIRED OR
 THIS OCCUPANCY. THE FIRE ALARM SHALL BE MONITORED
 UNLESS THE FACILTIY IS MANNED 24 HOURS A DAY.
  
 A KNOX BOX KEY SYSTEM IS REQUIRED FOR 24 HOUR EMERGENCY
 RESPONDER ACCESS.