Plan Review Notes For Permit 14080325 |
Permit Number |
14080325 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-08-12 14:38:15 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | THIS OCCUPANCY AND PROPOSED PLAN SHALL MEET OR EXCEED | | THE REQUIREMENTS OF NFPA 150, FIRE AND LIFE SAFETY IN | | ANIMAL HOUSING FACILITIES. | | | | THE BUILDING PLAN DOES NOT INCLUDE THE BUILDING SQUARE | | FOOTAGE AND CONSTRUCTION TYPE/CLASS, ROOF SYSTEM. | | | | A LIFE SAFETY PLAN, INCLUDING ALL OCCUPANCY COUNTS, | | HUMAN AND ANIMAL, COMMON PATHS OF TRAVEL, EXITS, EXIT | | DISCHARGES AND FIRE EXTINGUISHER LOCATIONS SHALL BE | | INCLUDED. | | | | AN EXIT PATH SHALL NOT EXCEED 75 FEET FROM ANY AREA OF | | THE BUUILDING. | | | | A NFPA 72 COMPLIANT FIRE ALARM SYSTEM IS REQUIRED OR | | THIS OCCUPANCY. THE FIRE ALARM SHALL BE MONITORED | | UNLESS THE FACILTIY IS MANNED 24 HOURS A DAY. | | | | A KNOX BOX KEY SYSTEM IS REQUIRED FOR 24 HOUR EMERGENCY | | RESPONDER ACCESS. |
|