2014-08-27 10:55:2014080325
 6710 S. DIXIE HWY
 POSH PET HOTEL
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 PROVIDE A LIGHTING DENSITY SUMMARY ON THE ELECTRIC PLAN
 WHICH SHOWS COMPLIANCE WITH THE FLORIDA BUILDING ENERGY
 CODE REQUIREMENTS. FBC ENERGY CONSERVATION 505.5;
 505.5.3; T. 505.5.3
  
 CONFIRM THAT THE INTERIOR AND EXTERIOR LIGHTING
 CONTROLS PROVIDED FUNCTION IN ACCORDANCE WITH THE
 FLORIDA ENERGY CODE. EXTERIOR AUTOMATIC CONTROLS SHALL
 BE CAPABLE OF RETAINING PROGRAMMING AND THE TIME
 SETTING DURING LOSS OF POWER FOR A PERIOD OF AT LEAST
 10 HOURS. VERIFY THE LIGHTING AND SIGN TIME CLOCKS HAVE
 BATTERY BACKUP. FBC ENERGY CONSERVATION 505.2
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION
 FOR THE ELECTRIC SERVICE, PANEL BOARDS AND MAIN
 DISCONNECTING MEANS. NEC 110.16, 110.22
  
 PROVIDE AN ELECTRICAL RISER PLAN OF THE ELECTRICAL
 SERVICE WITH A SUMMERY LOAD CALCULATION. PROVIDE PANEL
 BOARD SCHEDULES SHOWING THE BRANCH CIRCUITS AS
 BALANCED. INDICATE THE FAULT CURRENT RATINGS OF THE
 EQUIPMENT. VERIFY THE ELECTRICAL SERVICE MAINS SERVING
 THIS BUILDING ARE SIX OR LESS AND GROUPED IN ONE
 LOCATION. VERIFY SAFE WORKING CLEARANCE HAVE BEEN
 PROVIDED FOR THE SERVICE, PANEL BOARDS AND DISCONNECTS.
 NEC 110.26, 215.5, 230.71 240.24(D)
  
 VERIFY THE ELECTRICAL DISCONNECTING MEANS AND PANEL
 BOARDS HAVE A FAULT CURRENT RATING THAT IS SUFFICIENT
 AT NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE
 INTERRUPTED. INDICATE THE MAXIMUM AVAILABLE FAULT
 CURRENT AT THE SERVICE POINT FROM THE ELECTRICAL
 UTILITY. NEC 110.9, 110.10
  
 PROVIDE SHOW WINDOW LIGHTING RECEPTACLES. NEC 210.62
  
 PROVIDE A SIGN CIRCUIT AND DISCONNECT. NEC 600.5,
  
 VERIFY EXISTING HEATING AND AIR CONDITIONING EQUIPMENT
 HAVE A GFCI PROTECTED RECEPTACLE AVAILABLE WITHIN 25
 FEET. NEC 210.63
  
 NOTE: A SEPARATE PERMIT AND PLANS ARE REQUIRED FOR FIRE
 ALARM SYSTEMS, VIDEO, SECURITY, VOICE, POS, SITE
 LIGHTING, SIGNS AND DATA SYSTEMS
  
 ROBERT LECKY, CBO
 ELECTRICAL PLANS REVIEW
 561-373-3701
 [email protected]
  