2014-08-27 10:55:20 | 14080325 |
| 6710 S. DIXIE HWY |
| POSH PET HOTEL |
| |
| PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING |
| REVIEW COMMENTS. |
| |
| PROVIDE A LIGHTING DENSITY SUMMARY ON THE ELECTRIC PLAN |
| WHICH SHOWS COMPLIANCE WITH THE FLORIDA BUILDING ENERGY |
| CODE REQUIREMENTS. FBC ENERGY CONSERVATION 505.5; |
| 505.5.3; T. 505.5.3 |
| |
| CONFIRM THAT THE INTERIOR AND EXTERIOR LIGHTING |
| CONTROLS PROVIDED FUNCTION IN ACCORDANCE WITH THE |
| FLORIDA ENERGY CODE. EXTERIOR AUTOMATIC CONTROLS SHALL |
| BE CAPABLE OF RETAINING PROGRAMMING AND THE TIME |
| SETTING DURING LOSS OF POWER FOR A PERIOD OF AT LEAST |
| 10 HOURS. VERIFY THE LIGHTING AND SIGN TIME CLOCKS HAVE |
| BATTERY BACKUP. FBC ENERGY CONSERVATION 505.2 |
| |
| PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION |
| FOR THE ELECTRIC SERVICE, PANEL BOARDS AND MAIN |
| DISCONNECTING MEANS. NEC 110.16, 110.22 |
| |
| PROVIDE AN ELECTRICAL RISER PLAN OF THE ELECTRICAL |
| SERVICE WITH A SUMMERY LOAD CALCULATION. PROVIDE PANEL |
| BOARD SCHEDULES SHOWING THE BRANCH CIRCUITS AS |
| BALANCED. INDICATE THE FAULT CURRENT RATINGS OF THE |
| EQUIPMENT. VERIFY THE ELECTRICAL SERVICE MAINS SERVING |
| THIS BUILDING ARE SIX OR LESS AND GROUPED IN ONE |
| LOCATION. VERIFY SAFE WORKING CLEARANCE HAVE BEEN |
| PROVIDED FOR THE SERVICE, PANEL BOARDS AND DISCONNECTS. |
| NEC 110.26, 215.5, 230.71 240.24(D) |
| |
| VERIFY THE ELECTRICAL DISCONNECTING MEANS AND PANEL |
| BOARDS HAVE A FAULT CURRENT RATING THAT IS SUFFICIENT |
| AT NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE |
| INTERRUPTED. INDICATE THE MAXIMUM AVAILABLE FAULT |
| CURRENT AT THE SERVICE POINT FROM THE ELECTRICAL |
| UTILITY. NEC 110.9, 110.10 |
| |
| PROVIDE SHOW WINDOW LIGHTING RECEPTACLES. NEC 210.62 |
| |
| PROVIDE A SIGN CIRCUIT AND DISCONNECT. NEC 600.5, |
| |
| VERIFY EXISTING HEATING AND AIR CONDITIONING EQUIPMENT |
| HAVE A GFCI PROTECTED RECEPTACLE AVAILABLE WITHIN 25 |
| FEET. NEC 210.63 |
| |
| NOTE: A SEPARATE PERMIT AND PLANS ARE REQUIRED FOR FIRE |
| ALARM SYSTEMS, VIDEO, SECURITY, VOICE, POS, SITE |
| LIGHTING, SIGNS AND DATA SYSTEMS |
| |
| ROBERT LECKY, CBO |
| ELECTRICAL PLANS REVIEW |