Plan Review Notes
Plan Review Notes For Permit 14080325
Permit Number 14080325
Review Stop B
Sequence Number 1
Notes
Date Text
2014-08-27 16:38:04BUILDING PLAN REVIEW
 PERMIT: 14080325
 ADD: 6710 S DIXIE HWY
 CONT: RAPP CONSTRUCTION
 TEL: (561)842-3299
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. AUG. 27/2014
 ACTION: DENIED
  
 1) 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING
 OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA
 AND DOCUMENTS:
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 2. OCCUPANCY GROUP: 304.1 BUSINESS GROUP B. ANIMAL
 HOSPITALS, KENNELS AND POUNDS
 3. MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED
 (SEE TABLE 503).
 4. FIRE SUPPRESSION SYSTEMS SHALL INCLUDE: SCHEMATIC
 FIRE SPRINKLERS. FIRE SPRINKLERS YES OR NO
 5) LIFE SAFETY SYSTEMS SHALL BE DETERMINED AND SHALL
 INCLUDE THE FOLLOWING REQUIREMENTS:
 6) OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD : GROSS OR NET TABLE 1004.1.1
 MEANS OF EGRESS : EXIT ACCESS TRAVEL DISTANCES
  
 2) SHEET A3:
 2A) THE BUILDING HAS A OCCUPANT LOAD OF OVER 50
 OCCUPANTS, MANY OF THE DOORS SWING AGAINST THE MEANS OF
 EGRESS AND WILL NEED TO COMPLY WITH: 2010 FBC-B
 1008.1.2 DOOR SWING. DOORS SHALL SWING IN THE DIRECTION
 OF EGRESS TRAVEL WHERE SERVING AN OCCUPANT LOAD OF 50
 OR MORE PERSONS.
  
 2B) DOORS ALSO HAVE CARD READERS ON ALOT OF EGRESS
 DOORS, PLEASE COMPLY WITH 1008.1.4.4 ACCESS-CONTROLLED
 EGRESS DOORS.
  
 2C) DOORS ARE NOT NUMBERED TO IDENTIFY THERE LOCATION,
 ONLY THE TYPE OF DOOR. THERE ARE MANY DOORS THAT DO NOT
 MEET THE 2010 FL ACCESSIBILITY CODE. PLEASE REVIEW
 TABLE 404.2.4.1.
  
 2D) THERE ARE EXISITNG AS WELL AS NEW DOORS, THE 2010
 FBC-B 1008.1.1 SIZE OF DOORS. THE MINIMUM WIDTH OF EACH
 DOOR OPENING SHALL BE SUFFICIENT FOR THE OCCUPANT LOAD
 THEREOF AND SHALL PROVIDE A CLEAR WIDTH OF 32 INCHES
 (813 MM). CLEAR OPENINGS OF DOORWAYS WITH SWINGING
 DOORS SHALL BE MEASURED BETWEEN THE FACE OF THE DOOR
 AND THE STOP, WITH THE DOOR OPEN 90 DEGREES.
 2010 FL ACCESSIBILITY CODE 04.2.3 CLEAR WIDTH. DOOR
 OPENINGS SHALL PROVIDE A CLEAR WIDTH OF 32 INCHES (815
 MM) MINIMUM. CLEAR OPENINGS OF DOORWAYS WITH SWINGING
 DOORS SHALL BE MEASURED BETWEEN THE FACE OF THE DOOR
 AND THE STOP, WITH THE DOOR OPEN 90 DEGREES.
  
 3) THE 2010 FL ACCESSIBILITY CODE WILL REQUIRE
 ACCESSIBLE UPGRADES UP TO 20% OF THE CONTRACT VALUE OR
 $45,000.00 OF ADDITIONAL VALUE OF WORK. 202.4.1
 DISPROPORTIONATE COST. ALTERATIONS MADE TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL TO THE ALTERED AREA WILL BE
 DEEMED DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN
 THE COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO
 THE PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
  
 EITHER THE DESIGNER OR CONTRACTOR WILL NEED TO MAKE UP
 A ITEMIZED LIST WHERE THESE MONIES WILL BE SPENT IN
 ACCESSIBLE UPGRADES.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved