Date |
Text |
2014-08-27 16:38:04 | BUILDING PLAN REVIEW |
| PERMIT: 14080325 |
| ADD: 6710 S DIXIE HWY |
| CONT: RAPP CONSTRUCTION |
| TEL: (561)842-3299 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: WED. AUG. 27/2014 |
| ACTION: DENIED |
| |
| 1) 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING |
| OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA |
| AND DOCUMENTS: |
| 107.3.5.1 COMMERCIAL BUILDINGS: |
| 107.3.5.1.1 BUILDING |
| 2. OCCUPANCY GROUP: 304.1 BUSINESS GROUP B. ANIMAL |
| HOSPITALS, KENNELS AND POUNDS |
| 3. MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED |
| (SEE TABLE 503). |
| 4. FIRE SUPPRESSION SYSTEMS SHALL INCLUDE: SCHEMATIC |
| FIRE SPRINKLERS. FIRE SPRINKLERS YES OR NO |
| 5) LIFE SAFETY SYSTEMS SHALL BE DETERMINED AND SHALL |
| INCLUDE THE FOLLOWING REQUIREMENTS: |
| 6) OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: |
| OCCUPANCY LOAD : GROSS OR NET TABLE 1004.1.1 |
| MEANS OF EGRESS : EXIT ACCESS TRAVEL DISTANCES |
| |
| 2) SHEET A3: |
| 2A) THE BUILDING HAS A OCCUPANT LOAD OF OVER 50 |
| OCCUPANTS, MANY OF THE DOORS SWING AGAINST THE MEANS OF |
| EGRESS AND WILL NEED TO COMPLY WITH: 2010 FBC-B |
| 1008.1.2 DOOR SWING. DOORS SHALL SWING IN THE DIRECTION |
| OF EGRESS TRAVEL WHERE SERVING AN OCCUPANT LOAD OF 50 |
| OR MORE PERSONS. |
| |
| 2B) DOORS ALSO HAVE CARD READERS ON ALOT OF EGRESS |
| DOORS, PLEASE COMPLY WITH 1008.1.4.4 ACCESS-CONTROLLED |
| EGRESS DOORS. |
| |
| 2C) DOORS ARE NOT NUMBERED TO IDENTIFY THERE LOCATION, |
| ONLY THE TYPE OF DOOR. THERE ARE MANY DOORS THAT DO NOT |
| MEET THE 2010 FL ACCESSIBILITY CODE. PLEASE REVIEW |
| TABLE 404.2.4.1. |
| |
| 2D) THERE ARE EXISITNG AS WELL AS NEW DOORS, THE 2010 |
| FBC-B 1008.1.1 SIZE OF DOORS. THE MINIMUM WIDTH OF EACH |
| DOOR OPENING SHALL BE SUFFICIENT FOR THE OCCUPANT LOAD |
| THEREOF AND SHALL PROVIDE A CLEAR WIDTH OF 32 INCHES |
| (813 MM). CLEAR OPENINGS OF DOORWAYS WITH SWINGING |
| DOORS SHALL BE MEASURED BETWEEN THE FACE OF THE DOOR |
| AND THE STOP, WITH THE DOOR OPEN 90 DEGREES. |
| 2010 FL ACCESSIBILITY CODE 04.2.3 CLEAR WIDTH. DOOR |
| OPENINGS SHALL PROVIDE A CLEAR WIDTH OF 32 INCHES (815 |
| MM) MINIMUM. CLEAR OPENINGS OF DOORWAYS WITH SWINGING |
| DOORS SHALL BE MEASURED BETWEEN THE FACE OF THE DOOR |
| AND THE STOP, WITH THE DOOR OPEN 90 DEGREES. |
| |
| 3) THE 2010 FL ACCESSIBILITY CODE WILL REQUIRE |
| ACCESSIBLE UPGRADES UP TO 20% OF THE CONTRACT VALUE OR |
| $45,000.00 OF ADDITIONAL VALUE OF WORK. 202.4.1 |
| DISPROPORTIONATE COST. ALTERATIONS MADE TO PROVIDE AN |
| ACCESSIBLE PATH OF TRAVEL TO THE ALTERED AREA WILL BE |
| DEEMED DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN |
| THE COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO |
| THE PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS |
| EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF |
| TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING |
| AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE |
| ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING |
| RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS, |
| ENLARGING TOILET STALLS, INSULATING PIPES, OR |
| INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS |
| ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH |
| AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT, |
| INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT |
| TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING |
| AN INACCESSIBLE DRINKING FOUNTAIN. |
| |
| EITHER THE DESIGNER OR CONTRACTOR WILL NEED TO MAKE UP |
| A ITEMIZED LIST WHERE THESE MONIES WILL BE SPENT IN |
| ACCESSIBLE UPGRADES. |
| |
| A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |
| |