2014-08-13 10:04:55 | DATE: 8/13/2014 |
| PROJECT: FED EX REVISION |
| REVISION #14080241 PERMIT#: 13120825 |
| CODE: 2008 EDITION OF THE NEC |
| 2010 EDITION OF THE FBC |
| 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| |
| 1ST ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| 1) PROVIDE A LOAD CALCULATION TO INDICATE THE TOTAL |
| CONNECTED LOAD INCLUDING THE NEW 225AMP CIRCUIT FOR |
| CONVEYOR CONTROL PANEL. |
| 2) REVISE THE ONE LINE RISER DIAGRAM TO INDICATE |
| ADAQUATE WIRE SIZE TO SUPPORT THE 1600AMP MDP |
| NEC230.90(A), 310.16 |
| 3) REVISE THE RISER DIAGRAM TO ADDRESS THE LACK OF GFP |
| OF EQUIPMENT AS PER NEC 230.95 |
| 4) REVISE GROUNDING ELECTRODE CONDUCTOR SIZE TO THE |
| MAXIMUM 3/0CU. PER NEC 250.66 NOTES: WHERE MULTIPLE |
| SETS OF SERVICE-ENTRANCE CONDUCTORS ARE USED AS |
| PERMITTED IN 230.40, EXCEPTION NO. 2, THE EQUIVALENT |
| SIZE OF THE LARGEST SERVICE-ENTRANCE CONDUCTOR SHALL BE |
| DETERMINED BY THE LARGEST SUM OF THE AREAS OF THE |
| CORRESPONDING CONDUCTORS OF EACH SET. THE SERVICE |
| ENTRANCE CALLS FOR 4 SETS OF 4, 600MCM. PLEASE INDICATE |
| CONDUCTOR AND INSULATION TTYPE ON ALL WIRE. |
| 5) REVISE THE PANEL SCHEDULE MDP TO INCLUDE THE NEW |
| 225AMP CIRCUIT FOR CONVEYOR CONTROL PANEL. WPB |
| AMENDMENTS TO FBC CHAPER 1 SECTION 107.2.1 |
| 6) REVISE PANEL PP1 TO ADD NOTE "LO" TO INDICATE LOCK |
| ON DEVICE FOR THAT CIRCUIT. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT |
| /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM |
| ITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| SHEETS FOR COMPARATIVE REVIEW. |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |