2015-01-14 11:23:45 | DATE: 01/14/2015 |
| PROJECT: 36TH ST REAR BLDG |
| PERMIT#: 14080234 |
| CODE: 2008 EDITION OF THE NEC |
| 2010 EDITION OF THE FBC, WPB AMENDMENTS TO THE FBC, |
| CHAPTER 1, ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| 4TH ELECTRICAL PLAN REVIEW |
| ACTION: APPROVED WITH EXCEPTION |
| |
| PROVIDE AN AS BUILT FOR ELECTRICAL INSPECTOR ON SITE |
| PER EXISTING CONDITIONS. |
| |
| 1) FBC-WPB AMENDMENTS 107.3.5 |
| INDICATE THE TRUE SCOPE AND EXTENT OF ELECTRICAL |
| IMPROVEMENTS. THE APPLICATION STATES "INTERIOR |
| IMPROVEMENTS AND WINDOW REPLACEMENT" THE PLAN PROVIDES |
| ELECTRICAL DETAILS AND NOTES. CLARIFICATION IS |
| REQUIRED. INDICATE WHAT IS EXISTING TO REMAIN. WHAT IS |
| REMOVED AND OR RELOCATED AND WHAT IS COMPLETELY NEW OR |
| SIMPLY REPLACED. |
| |
| 2) PROVIDE A RISER DIAGRAM, LOAD CALCULATION AND A |
| PANEL SCHEDULE. NEC 215.5, 220, 408.4 |
| |
| 3) IDENTIFY THE LOCATION AND SIZE OF THE ELECTRICAL |
| SERVICE, MAIN DISCONNECT, PANEL, CONDUITS AND FEEDER |
| CONDUCTORS. |
| |
| 4) IDENTIFY THE CIRCUITRY FOR THE OUTLETS AND LIGHTS |
| THROUGHOUT TO COINCIDE WITH THE PANEL CIRCUIT |
| DIRECTORY. FBC, WPB AMENDMENTS 107.3.2 |
| |
| 5) VERIFY RECEPTACLES SHALL BE INSTALLED SUCH THAT NO |
| POINT MEASURED HORIZONTALLY ALONG THE FLOOR LINE IN ANY |
| WALL SPACE IS MORE THAN 1.8 M (6 FT) FROM A RECEPTACLE |
| OUTLET OR 24" FOR KITCHEN COUNTERTOPS. 210.52(A)(1), |
| 210.52(C)(1), |
| |
| 6) ALL HABITABLE LIVING AREA REQUIRES A SWITCHED LIGHT |
| OR SWITCH CONTROLLED OUTLET. NEC 210.70. THE LIVING |
| ROOM HAS NO SWITCH CONTROLLED LIGHT OUTLET. |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |